68
3. Warn 0020
AC fan (invisible
from the outside)
inside the inverter is
working abnormally
1. The fan is blocked;
2. The power supply
circuit of the fan
goes wrong;
3. The state test
circuit of the fan
goes wrong;
4. The service life of
the fan has
expired.
1. Observe for 5
minutes to see
whether the alarm
will be eliminated
automatically;
2. Conduct simple
inspection;
3. Contact our
after-sales service
center
4. Warn 0030
Internal warn
Internal memory
storage error
1. Observe for 5
minutes to see
whether the alarm
will be eliminated
automatically;
2. Contact our
after-sales service
center
5. Warn 0040
Internal warn
DC or AC SPD is in
the off-state
1. Observe for 5
minutes to see
whether the alarm
will be eliminated
automatically;
2. Contact our
after-sales service
center
6. Warn 0050
Internal warn
Temperature sensor
is in the failure mode
(short circuit or open
circuit)
1. Observe for 5
minutes to see
whether the alarm
will be eliminated
automatically;
2. Contact our
after-sales service
center