70
11. Warn0010
Internal warn
DC breaker 2 is
abnormal
1.
Observe for 5
minutes to see
whether the alarm
will be eliminated
automatically;
2.
Contact our
after-sales service
center
12. Warn0011
Internal warn
DC breaker 3 is
abnormal
1.
Observe for 5
minutes to see
whether the alarm
will be eliminated
automatically;
2.
Contact our
after-sales service
center
Protect
1.
Over-temperature
Environmental
temperature, or
temperature inside
inverter is too high
1. The external
environmental
temperature of the
inverter is too
high;
2. The fan is blocked
1. Please confirm that
the environmental
temperature is
within the working
range;
2. Check whether the
air fan is blocked;
3. Check whether
cooling fan is
blocked;
4. Observe for 30
minutes to see
whether the alarm
will be eliminated
automatically;
5. Contact our
after-sales service
center