11.3 Fault and Troubleshooting on the LCD screen
Before you contact our after-sales service center, you are able to find most faults and solutions in
Table 11-1 for troubleshooting. There are three categories of fault alert statuses: Warn, Protect and
Fault. When there is a “Warn”, the system only reminds customers of the problem while it doesn’t
change the operation mode. When there is a “Protect”, the system will turn into fault mode and
turn to normal operation when the “Protect” disappears. When there is a “Fault”, the system will
stop working and remain standby until the system is reset or the inverter is repaired to eliminate
the fault. For system resetting, manually shutdown the inverter through LCD, and disconnect the
PV DC circuit breaker. Then execute discharging, wait for 5s and turn on the grid circuit breaker
to execute the first system transmission again.
Table 11-1 Troubleshooting
Warn/Protect
/Fault
Definition
Possible Causes
Recommended
Solutions
Warn
1. Internal
communication
failure
Inverter internal
communication in
failure
1.Communication
circuits inside
inverter are loose;
2.LCD software
problem
1. Observe for 5
minutes to see
whether the alarm
will be eliminated
automatically;
2. Conduct simple
inspection;
3. Contact our
after-sales service
center.
2. Warn 0010
DC fan (invisible
from the outside)
inside the inverter is
working abnormally
1. The fan is blocked;
2. The power supply
circuit of the fan
goes wrong;
3. The state test
circuit of the fan
goes wrong;
4. The service life of
the fan has
expired.
1. Observe for 5
minutes to see
whether the alarm
will be eliminated
automatically;
2. Conduct simple
inspection;
3. Contact our
after-sales service
center.