Warnings
POWER DOWN
IW1-1
Possible cause:
Power outage or switching off the controller
on the main switch (0/1) unrelated in which operation phase the
burner is in, including also the phase OFF.
Boiler status:
The information is written in the warning history
and is not announced on the screen.
The record time is the
moment of the power outage/switching off the controller on the
main switch.
POWER UP
IW1-2
Possible cause:
Return of power or switching on the controller
on the main switch (0/1).
Boiler status:
The information is written in the warning history
and is not announced on the screen.
The record time is the
moment of the power return/switching on the controller on the
main switch.
ENTERING INTO
STATE F1
IW1-3
Possible cause:
The tube backfilling sensor has signaled the
backfilling of the pellet supply tube.
Boiler status:
The information is written/recorded in the
warning history and is not announced on the screen.It is factory
active only for CPPL 90.
The boiler
operates in a special
regime
(
reduces the pellet supply into the burner) with the goal
to continue the work in a standard regime, if it fails during the
set time the error E9_1 or E9_2 is notified.
Troubleshooting:
Check the backfilling of the burner grate,
burner combustion chamber, boiler combustion chamber, flue
gas passages, backfilling of the flue and chimney, check if the
burner grate is
properly set in the burner (check that the burner
grate is not set ON the electric heater – this is valid for CPPL
14 – 50), check if the pellets are too humid, inadequate
dimensions or pellet quality (for this burner setting the diameter
6 mm),
p
ossible hole in the flexible tube, to big pellet supply
(too low fan's rpm).
Technical instructions CONTROLLER -
CPREG-Touch
104