CD Automation srl
REVO M
User’s Manual
CD-Eng-REVO-M-2PH-30-40A-Thyristors-Units
44
21
Maintenance
In order to have a corrected cooling, the user must clean the heat-sink and the protective grill of the
fans. The frequency of this servicing depends on environmental pollution.
Also check periodically if the screw for the power cables and safety earth are tightened correctly
(See Connection Diagram)
21.1
Trouble Shooting
Small problems sometimes can be solved locally with the help of the below tab of trouble shooting.
If you don’t succeed, contact us or your nearest distributor.
Symptom
Indication on
front unit
Possible reasons of the
symptom
Actions
Load current
doesn’t flow
Green LED (ON)
light OFF
No Auxiliary Voltage
No input signal
Reversed polarities of input
signal
Give auxiliary voltage supply
(See
Connection Diagram
)
Provide to give input signal
Reverse the input signal polarity
Green LED (ON)
light ON
Fuse failure
Load connection interruption
Load failure: The yellow led (HB)
is light on (with HB option)
Thyristor fault: The red led (SC)
is light on (with HB option)
Change the fuse
Check the wiring
Check the load
Change the thyristor module
Load current flow
also without input
signal
Red LED (SC)
light on
Wrong wiring
SCR short circuit
Check the wiring
Change the thyristor module
Current flows at
nominal value but
Yellow LED
(HB/SC) is light
on
Yellow LED (HB)
light on
or
Red LED (SC)
light on
HB circuit not tuned
Current transformers not
properly wired
Make HB calibration procedure
Check current transformers
wiring
Thyristor unit
doesn’t work
properly
Auxiliary voltage supply out of
limits
Wrong input signal selection.
Wrong input signal calibration
(out of range)
Verify the auxiliary voltage
supply
Control input signal setting.
Check input setting
21.2
Warranty condition
CD Automation gives a 12 months warranty to its products.
The warranty is limited to repairing and parts substitution in our factory and does
exclude products not properly used and fuses.
Warranty does not include products with serial numbers deleted. The faulty product
should be shipped to CD Automation at customer’s cost and our Service will evaluate
if product is under warranty terms.
Substituted parts remain of CD Automation property.
Содержание Revo M 2PH
Страница 2: ...CD Automation srl REVO M User s Manual CD Eng REVO M 2PH 30 40A Thyristors Units 2 ...
Страница 13: ...CD Automation srl REVO M User s Manual CD Eng REVO M 2PH 30 40A Thyristors Units 13 8 2 Order Code ...
Страница 21: ...CD Automation srl REVO M User s Manual CD Eng REVO M 2PH 30 40A Thyristors Units 21 TOP VIEW DOWN VIEW ...
Страница 24: ...CD Automation srl REVO M User s Manual CD Eng REVO M 2PH 30 40A Thyristors Units 24 12 1 Scroll the parameters ...
Страница 45: ...CD Automation srl REVO M User s Manual CD Eng REVO M 2PH 30 40A Thyristors Units 45 ...