CD Automation srl
REVO M
User’s Manual
CD-Eng-REVO-M-2PH-30-40A-Thyristors-Units
28
12.3
Setup Menu
Push simultaneously
L/R
and
F
for few seconds to
access
to the menu (
flashing).
Select by arrows
UP
and
DOWN :
then press
F.
Select by arrows
UP
and
DOWN :
as password
then press
F.
You have access to the parameter on
menu.
Select by arrows
UP
and
DOWN
the required parameter.
If the parameter is
Write/Read (W/R)
press
F
(parameter flashing) then select by
arrows
UP
and
DOWN
the required velue, press
F
to set the new value.
Push simultaneously
L/R
and
F
for few seconds to
Exit
from the menu
Set Firing type:
Parameter
Display
Parameter
Name
Contents
UM
Default
Value
UM
Min
Value
DEC
Max
Value
DEC
Min
Value
UM
Max
Value
UM
Write
Read
Fir
Firing mode
Selection
SW
2
*
0
1024
0
1024
R/W
*Default Value if not specified in the Order Code
Set HB sensitivity:
This parameter defines the threshold of resistance that activates the HB alarm
This value is in percentage respect the nominal resistance load value
Parameter
Display
Parameter
Name
Contents
UM
Default
Value
UM
Min
Value
DEC
Max
Value
DEC
Min
Value
UM
Max
Value
UM
Par.
Type
Hb_S
HB sensitivity
%
100
0
100
0
100
R/W
Set HB Delay:
This parameter set a delay to have HB alarm active
Parameter
Display
Parameter
Name
Contents
UM
Default
Value
UM
Min
Value
DEC
Max
Value
DEC
Min
Value
UM
Max
Value
UM
Par.
Type
Hb_S
HB delay
sec
20
0
255
0
255
R/W
Set FeedBack type:
This parameter selects the Feed-back type.
Parameter
Display
Parameter
Name
Contents
UM
Default
Value
UM
Min
Value
DEC
Max
Value
DEC
Min
Value
UM
Max
Value
UM
Par.
Type
FEEd
Feed back
selection
SW
1
*
0
1024
0
1024
R/W
*Default Value if not specified in the Order Code
Sample Values and Note
1 = Zero Crossing
2 = Burst Firing
Sample Values and Note
0 = V2
1 = NO Feed Back
32 = Voltage V
64 = Current I
128 = Power V X I
Содержание Revo M 2PH
Страница 2: ...CD Automation srl REVO M User s Manual CD Eng REVO M 2PH 30 40A Thyristors Units 2 ...
Страница 13: ...CD Automation srl REVO M User s Manual CD Eng REVO M 2PH 30 40A Thyristors Units 13 8 2 Order Code ...
Страница 21: ...CD Automation srl REVO M User s Manual CD Eng REVO M 2PH 30 40A Thyristors Units 21 TOP VIEW DOWN VIEW ...
Страница 24: ...CD Automation srl REVO M User s Manual CD Eng REVO M 2PH 30 40A Thyristors Units 24 12 1 Scroll the parameters ...
Страница 45: ...CD Automation srl REVO M User s Manual CD Eng REVO M 2PH 30 40A Thyristors Units 45 ...