CD Automation srl
REVO M
User’s Manual
CD-Eng-REVO-M-2PH-30-40A-Thyristors-Units
39
17.2
Supply the Electronic Board
The REVO M thyristor unit, to work, requires a voltage supply for the electronic boards. The Max
consumption is 10VA.
The voltage supply for the electronic boards is configured in line with customer requirements that are
defined in the Order Code. The Order Code is written on the identification label.
Warning:
Before connecting or disconnecting the unit check that power and control cables
are isolated from voltage sources.
Terminal M4
M4
Description
1
Voltage Supply for Electronic Boards (Auxiliary Voltage)
2
Not Used
3
Voltage Supply for Electronic Boards (Auxiliary Voltage)
To change auxiliary supply voltage sold the correct link-jumper on Revo M board
The type of mounted transformer depends of the chosen Voltage in the order code.
Trasformer Type
Link-Jumper JP1+JP2
Link-Jumper JP3
TR-605 120V
90:130V
170:265V
TR-605 230V
170:265V
300:530V
TR-605 300V
230:345V
510:690V
If the Auxiliary Voltage (written on the identification label) is different from Supply Voltage (to the load),
use an external transformer with primary equal to load voltage and secondary equal to the Auxiliary
Voltage
M4
Содержание Revo M 2PH
Страница 2: ...CD Automation srl REVO M User s Manual CD Eng REVO M 2PH 30 40A Thyristors Units 2 ...
Страница 13: ...CD Automation srl REVO M User s Manual CD Eng REVO M 2PH 30 40A Thyristors Units 13 8 2 Order Code ...
Страница 21: ...CD Automation srl REVO M User s Manual CD Eng REVO M 2PH 30 40A Thyristors Units 21 TOP VIEW DOWN VIEW ...
Страница 24: ...CD Automation srl REVO M User s Manual CD Eng REVO M 2PH 30 40A Thyristors Units 24 12 1 Scroll the parameters ...
Страница 45: ...CD Automation srl REVO M User s Manual CD Eng REVO M 2PH 30 40A Thyristors Units 45 ...