CD Automation srl
REVO M
User’s Manual
CD-Eng-REVO-M-2PH-30-40A-Thyristors-Units
14
9
Technical Specifications
9.1
General features:
Cover and Socket material:
PolymericV2
Mounting:
DIN bar (thickness type 1mm Max)
Utilization Category
AC-51 AC-55b
IP Code
20
Method of Connecting
Load in Delta, Load in Star
Auxiliary voltage, power supply Control Circuit:
90:130V
(8 VA Max)
170:265V
(8 VA Max)
230:345V
(8 VA Max)
300:530V
(8 VA Max)
510:690V
(8 VA Max)
600:760V
(8 VA Max)
Relay output for Heater Break Alarm
(only with HB option):
0.5A a 125VAC
9.2
Input features:
Logic input SSR:
4 ÷ 30Vdc 5mA Max (ON
4Vdc OFF
1Vdc)
Analog Input V:
0 ÷ 10Vdc impedance 15 K ohm
Analog Input A:
4 ÷ 20mA impedance 100 ohm
POT
10 K ohm min.
Digital Input
4 ÷ 30Vdc 5mA Max (ON
4Vdc OFF
1Vdc)
9.3
Output features(power device):
Nominal current in continuous service:
See order code
Max peak current (10ms)
360A for unit type 030
540A for unit type 035
700A for unit type 040
Nominal Voltage range
Ue
:
24÷600V
Repetitive peak reverse voltage
Uimp
:
1200V (480V) 1600V (600V)
Latching current:
250mA
Leakage current:
15mA eff
FUSE I²T value suggested at 500Vac tp=10msec:
525 A²s for unit type 030
1260 A²s for unit type 035
1260 A²s for unit type 040
Frequency range:
47÷70Hz
Power loss (I=Inom):
76W for unit type 030
88W for unit type 035
100W for unit type 040
Isolation Voltage
Ui
:
2500Vac
Содержание Revo M 2PH
Страница 2: ...CD Automation srl REVO M User s Manual CD Eng REVO M 2PH 30 40A Thyristors Units 2 ...
Страница 13: ...CD Automation srl REVO M User s Manual CD Eng REVO M 2PH 30 40A Thyristors Units 13 8 2 Order Code ...
Страница 21: ...CD Automation srl REVO M User s Manual CD Eng REVO M 2PH 30 40A Thyristors Units 21 TOP VIEW DOWN VIEW ...
Страница 24: ...CD Automation srl REVO M User s Manual CD Eng REVO M 2PH 30 40A Thyristors Units 24 12 1 Scroll the parameters ...
Страница 45: ...CD Automation srl REVO M User s Manual CD Eng REVO M 2PH 30 40A Thyristors Units 45 ...