Heater Break alarm and SCR short circuit (HB Option)
Caution:
to work properly the load must be powered at least about 160msec.
The Heater Break circuit read the load resistance with an Internal voltage transducer and Internal
current transformer (C.T.), to calculate the resistance (V/I).
Minimum current is 10% of the current transformer size.
If load current is below this value the Heater Break Alarm doesn’t work properly.
14.1
Heater break Calibration procedure
An automatic function sets the Heater Break Alarm ,when write in the parameter
the load current
and in the parameter
the load voltage.
If the load resistance increases due to a partial or total load failure ,the HB alarm become ON and alarm
relay change status.
You can Adjust the sensibility of HB alarm by using the parameter
This parameter is set between
1 and 255% of the nominal resistance.
This parameter is the maximum increment of the resistance Load to establish the HB Alarm.
There is also
parameter to set a delay to have HB alarm active.
14.2
HB alarm contact (digital output)
The Revo unit with HB option, is supplied with Heater Break alarm contact normally opened (NO):
In normal conditions (without alarm) and with auxiliary power supply, the contact to the terminals
has opened (relay coil energized).
In alarm condition or without auxiliary power supply the contact to the terminals is closed (relay coil
not energized).
This alarm can be configured in order to activate itself after that one of these alarms occours:
HB and SC alarm are active.
Only HB alarm is active.
Only SC alarm is active.
Содержание Revo M 2PH
Страница 2: ...CD Automation srl REVO M User s Manual CD Eng REVO M 2PH 30 40A Thyristors Units 2 ...
Страница 13: ...CD Automation srl REVO M User s Manual CD Eng REVO M 2PH 30 40A Thyristors Units 13 8 2 Order Code ...
Страница 21: ...CD Automation srl REVO M User s Manual CD Eng REVO M 2PH 30 40A Thyristors Units 21 TOP VIEW DOWN VIEW ...
Страница 24: ...CD Automation srl REVO M User s Manual CD Eng REVO M 2PH 30 40A Thyristors Units 24 12 1 Scroll the parameters ...
Страница 45: ...CD Automation srl REVO M User s Manual CD Eng REVO M 2PH 30 40A Thyristors Units 45 ...