CD Automation srl
REVO M
User’s Manual
CD-Eng-REVO-M-2PH-30-40A-Thyristors-Units
29
Cycle Time:
The Cycle Time is the time which the Thyristor modulates to obtain the power demand.
Parameter
Display
Parameter
Name
Contents
UM
Default
Value
UM
Min
Value
DEC
Max
Value
DEC
Min
Value
UM
Max
Value
UM
Par.
Type
ctiN
Cycle time
mSec
x50
60
0
255
0
255
R/W
Burst Firing Cycles number:
It defines the number of voltage cycles in ON condition at 50% of power demand
Parameter
Display
Parameter
Name
Contents
UM
Default
Value
UM
Min
Value
DEC
Max
Value
DEC
Min
Value
UM
Max
Value
UM
Par.
Type
bF_n
Burst Firing
Cycles
Cycle
4*
1
255
1
255
R/W
*Default Value if not specified in the Order Code
Load Type:
Parameter
Display
Parameter
Name
Contents
UM
Default
Value
UM
Min
Value
DEC
Max
Value
DEC
Min
Value
UM
Max
Value
UM
Par.
Type
Load
Load Type
SW
0
0
3
0
3
R/W
Sample Values and Note
Only with Fir = Zero Crossing
With a Cycle time at 4 sec:
25%-> 1sec 0n+3sec off
50%-> 2sec 0n+2sec off
75%-> 3sec 0n+1sec off
Sample Values and Note
Only with Fir = Burst Firing
Sample Values and Note
0 = STAR
2 = DELTA
Cycle Time
Time
25%
ON
OFF
50%
75%
100%
Содержание Revo M 2PH
Страница 2: ...CD Automation srl REVO M User s Manual CD Eng REVO M 2PH 30 40A Thyristors Units 2 ...
Страница 13: ...CD Automation srl REVO M User s Manual CD Eng REVO M 2PH 30 40A Thyristors Units 13 8 2 Order Code ...
Страница 21: ...CD Automation srl REVO M User s Manual CD Eng REVO M 2PH 30 40A Thyristors Units 21 TOP VIEW DOWN VIEW ...
Страница 24: ...CD Automation srl REVO M User s Manual CD Eng REVO M 2PH 30 40A Thyristors Units 24 12 1 Scroll the parameters ...
Страница 45: ...CD Automation srl REVO M User s Manual CD Eng REVO M 2PH 30 40A Thyristors Units 45 ...