Wiring instructions
The Thyristor unit could be susceptible to interferences lost by near equipments or by the power supply,
for this reason in accord to the fundamental practices rules is opportune take some precautions:
The coil contactor, the relays and other inductive loads must be equipped with opportune RC filter.
Use shielded bipolar cables for all the input and output signals.
The signal cables must not be near and parallel to the power cables.
Local regulations regarding electrical installation should be rigidly observed.
Use copper cables and wires rated for use at 75°C only.
Power cable torque (suggested)
Type
Connector
Type
Torque
Lb-in (N-m)
Wire Range
mm²(AWG )
MAX Current
Terminals
Wire Terminals
UL Listed (ZMVV)
030
035
040
Screw M5
26.6 (3.0)
1.5-10 (16-8)
40A
Rigid / Flexible
Spade Terminal
Cable dimensions of the Command Terminals
0.5
mm² (AWG 18)
Cable dimensions of the Earth (suggested)
6
mm² (AWG 10)
Warning:
Before connecting or disconnecting the unit check that power and control cables
are isolated from voltage sources.
Terminal
Description
L1
Line Input Phase 1
T1
Load Output Phase 1
L3
Line Input Phase 2
T3
Load Output Phase 2
Содержание Revo M 2PH
Страница 2: ...CD Automation srl REVO M User s Manual CD Eng REVO M 2PH 30 40A Thyristors Units 2 ...
Страница 13: ...CD Automation srl REVO M User s Manual CD Eng REVO M 2PH 30 40A Thyristors Units 13 8 2 Order Code ...
Страница 21: ...CD Automation srl REVO M User s Manual CD Eng REVO M 2PH 30 40A Thyristors Units 21 TOP VIEW DOWN VIEW ...
Страница 24: ...CD Automation srl REVO M User s Manual CD Eng REVO M 2PH 30 40A Thyristors Units 24 12 1 Scroll the parameters ...
Страница 45: ...CD Automation srl REVO M User s Manual CD Eng REVO M 2PH 30 40A Thyristors Units 45 ...