13
Input output signal
13.1
Digital Input
The REVO M thyristor unit has 2 digital inputs opto-isolated to 24Vdc 5 mA.
You can activate the inputs with the internal supply or with an external source for example the PLC.
13.1.1
Start/Stop (Terminal 3 of M2)
This is the start command (Enable) of the REVO M.
If you Remove the Start command the REVO M thyristor unit will be stopped and the output will return
at zero.
13.1.2
Configurable Input (Terminal 4 of M2)
This digital input is configured by the parameter
and could perform different functions:
Enable:
This function forces the output at zero.
Feed-Back Selection:
With this function, when you active the input, the feed-back setted in the parameter
change in
Voltage Feed-Back (V).
Analog/Digital Setpoint(Local/Remote):
With this function, when you active the input, the setpoint reference change from Analog input to
Digital value in bumpless mode, setted in the parameter
. The parameter SP is not stored in
memory.
13.2
Digital Output terminal
(terminal
14-15-16 of M1)
The REVO M thyristor unit has 1 relay output on terminal 14-15-16 of terminal block M1
(Max 500mA, 125Vac). The functionality of this output cane be setted with the parameter
This digital output can be configured in order to activate itself after that one of these alarms occours:
HB and SC alarm are active.
Only HB alarm is active.
Only SC alarm is active.
13.3
Analog Input
Primary Input (Terminals 5 and 6 of M2)
The REVO M thyristor unit has 1 analog inputs (0÷10V, 0÷20mA, 4÷20mA ecc) for the analog setpoint.
The primary input is already configured in line with customer requirements that are defined in the Order
Code. The Order Code is written on the identification label.
However, if you wish to change the primary input (ex. from 0÷10V to 0÷20mA, 4÷20mA).
see par. Analog Inputs 17.3. for details
Содержание Revo M 2PH
Страница 2: ...CD Automation srl REVO M User s Manual CD Eng REVO M 2PH 30 40A Thyristors Units 2 ...
Страница 13: ...CD Automation srl REVO M User s Manual CD Eng REVO M 2PH 30 40A Thyristors Units 13 8 2 Order Code ...
Страница 21: ...CD Automation srl REVO M User s Manual CD Eng REVO M 2PH 30 40A Thyristors Units 21 TOP VIEW DOWN VIEW ...
Страница 24: ...CD Automation srl REVO M User s Manual CD Eng REVO M 2PH 30 40A Thyristors Units 24 12 1 Scroll the parameters ...
Страница 45: ...CD Automation srl REVO M User s Manual CD Eng REVO M 2PH 30 40A Thyristors Units 45 ...