8
Table 2 - Electrical data
42FMH
009
016
020
030
033
Operating voltage
V
220-230
220-230
230
400
230
400
230
400
Nominal power input*
kW
0.38
0.68
0.87
0.87
0.96
0.96
1.10
1.10
Nominal current drawn*
A
1.85
3.00
3.85
2.25
4.25
2.50
4.85
4.85
Starting current
A
9.25
15
17
9.90
23
13.40
23
13.40
42FMH
037
057
058
062
068
Operating voltage
V
230
400
230
400
230
400
230
400
230
400
Nominal power input*
kW
1.35
1.35
1.95
1.95
2.70
2.70
3.45
3.45
4.00
4.00
Nominal current drawn*
A
5.90
3.50
8.50
5.10
11.75
7.05
15.00
9.00
17.40
10.45
Starting current
A
30.70
17.80
44.20
25.40
50.60
40.20
93.40
53.90
93.40
53.90
* For nominal air flow
Note: Models 009 and 016 are single-phase, all others are three-phase.
Tabella 2 - Caratteristiche elettriche
42FMH
009
016
020
030
033
Tensione di funzionamento
V
220-230
220-230
230
400
230
400
230
400
Assorbimento nominale di potenza*
kW
0,38
0,68
0,87
0,87
0,96
0,96
1,10
1,10
Corrente nominale*
A
1,85
3,00
3,85
2,25
4,25
2,50
4,85
4,85
Corrente di spunto
A
9,25
15
17
9,90
23
13,40
23
13,40
42FMH
037
057
058
062
068
Tensione di funzionamento
V
230
400
230
400
230
400
230
400
230
400
Assorbimento nominale di potenza*
kW
1,35
1,35
1,95
1,95
2,70
2,70
3,45
3,45
4,00
4,00
Corrente nominale*
A
5,90
3,50
8,50
5,10
11,75
7,05
15,00
9,00
17,40
10,45
Corrente di spunto
A
30,70
17,80
44,20
25,40
50,60
40,20
93,40
53,90
93,40
53,90
*Con portata d'aria nominale
Nota: I modelli 009 e 016 sono adatte per alimentazione monofase, tutti gli altri modelli sono adatte per alimentazione trifase.
GB
I