pCOWeb
+030220966 – rel. 1.1 – 12.12.2017
83
MODBUS TCP/IP MAPS
APPENDIX J
Modbus TCP/IP service allows to share pCO variables via Modbus TCP/IP protocol. As shown in Section 0, two different maps are available. The first map is
kept for compatibility reasons and refers to the oldest firware versions of
pCOWeb
(up to v.1.4.x). For these versions, the following map holds:
pCOWeb
Index
Logical
Addressing
Modicon
Compatible
Analog
1
1
2
2
2
3
…
…
…
207
207
208
…
…
…
5000
5000
5001
Integer
1
5001
5002
2
5002
5003
…
…
…
207
5207
5208
…
…
…
5000
10000
10001
Digital
1
1
2
2
2
3
…
…
…
207
207
208
…
…
…
2048
2048
2049
As a consequence, some values are not reachable (values in
red
).
Starting from version 1.5.x and up to version 2.0.x, the map has been modified (so that all variables are actually reachable), as follows:
pCOWeb
Index
Logical
Addressing
Modicon
Compatible
Analog
1 1 2
2 2 3
… … …
207 207 208
… … …
5000 5000 5001
Integer
1 5002
5003
2 5003
5004
… … …
207 5208 5209
… … …
5000 10001 10002
Digital
1 1 2
2 2 3
… … …
207 207 208
… … …
2048 2048 2049