“Messages”
: Notification Messages allow customization of the strings identifying the events for integer and analog variables (
Figure 4.r
).
The settings in this window will only be used for e-mail and SNMP TRAP/INFORM messages and will be common to the events generated by all the
integer and analog variables.
In the e-mail notifications, the suitable string will be automatically added to the “Subject” field, separated by a dash; in the SNMP TRAP notifications, the
OID will be included automatically, with the corresponding string and contents, based on the event, as follows (see 6.2 on page 57):
1.3.6.1.4.1.9839.1.3.1.1.0
(OID for the Alarm fired event string)
1.3.6.1.4.1.9839.1.3.1.2.0
(OID for the Alarm reentered event string)
Figure 4.r - Setting the strings sent for Activation - Return
SETTINGS AVAILABLE:
Alarm fired: string that will be included in the notifications when the threshold is exceeded.
Alarm reentered: string that will be included in the notifications when returning back below the threshold, with hysteresis.
4.3.4
Setting the notifications set upon variations in the variables
IMPORTANT: Some settings described below (“Event Handlers”, “Trap Configuration” and “E-Mail Configuration”) are also used for the scheduled events (see
section 4.3.5 on page 28).
NOTE: all the following settings are valid from when they are confirmed; the
pCOWeb
does not need to be rebooted.
PROCEDURE
1.
Open the tab for setting the events corresponding to the
DIGITAL
variables (
2.
Figure
4.s
).
3.
In the page will be displayed all the Digital variables available for enabling the events relating to the variation of all the digital variables (
4.
Figure
4.s
). Moving the mouse, for example, over the section relating to digital variable 1 shows the tooltip “Digital Variable 1”; clicking opens the window,
divided into three sections, for setting the events linked to digital variable 1.
IMPORTANT: The range of variables related to the notifications goes from 0 to 207, even if the ModBus Extended protocol is running. Variables’ addresses
for notifications can go just from 0 to 207.
IMPORTANT: The Submit buttons only save the values for the corresponding section.
Figure 4.s - Events generated by digital variables
Type:
Digital
Variable:
1
: the settings in window only refer to the digital variable with index 1.