Code Description
Def Min Max UOM User
User
terminal
Master
0 = delay disabled
Door switch with stopping control (par. DIE)
Door open:
l
stop control (solenoid/compressor and evaporator fans off); alternatively, control can be kept active by
setting parameter DIP (see the description below);
l
light on (see par. DOE);
l
ALARM flashing;
l
disable temperature alarms.
Door closed:
l
resume control;
l
light off (see par. DOE) with delay set by par. H14;
l
ALARM stops flashing;
l
enable temperature alarms with delay Ad after bypass time defined by par. Add.
Code Description
Def Min Max UOM User
User
terminal
DIE
Assign door switch with solenoid/comp. and evap. fans OFF
digital input - see DIA
0
-1
5
-
S
NO
DOE Assign light digital output - see DOA
4
0
4
-
S
NO
H14 Time light stays on after closing the door
0
0 240 min
U
NO
Ad
Delay time for high and low temp. alarms (AH, AL)
120 0 240 min
U
YES
Add High temp. alarm bypass time for door open
30
1 240 min
U
NO
Fig.5.c
Important:
check compatibility of disabling/delaying the alarm with the site’s HACCP procedures.
Note:
l
when control resumes, the compressor times are observed (see the paragraph “Compressor”);
l
if the door remains open for longer than the value of par. Add, control resumes in any case. The
light remains on, the measurement shown on the display flashes, the buzzer and the alarm relay
are activated, and the temperature alarms are enabled with delay Ad.
ENG
0300086EN rel. 1.0 – 04.09.2018
5. Functions |
43
Содержание MPXone ACS00CB000010
Страница 2: ......
Страница 6: ......
Страница 17: ...2 6 1 Panel model Fig 2 l ENG MPXone 0300086EN rel 1 0 04 09 2018 2 Installation 17...
Страница 18: ...ENG 2 6 2 DIN rail model Fig 2 m 18 2 Installation MPXone 0300086EN rel 1 0 04 09 2018...
Страница 22: ...ENG DIN Fig 2 s RS485 supervisor network Fig 2 t Fig 2 u 22 2 Installation MPXone 0300086EN rel 1 0 04 09 2018...
Страница 107: ......