Code
Description
Def Min Max
UOM User
User
terminal
PM2
MOP: integral time
10
0
240
s
M
NO
PM3
MOP: alarm delay
0 = function disabled
0
0
999
s
S
NO
PM4
MOP: function activation delay when starting control
2
0
240
s
M
NO
PM5
MOP: close solenoid valve
0/1 = No/Yes
0
0
1
-
S
NO
PM6
MOP: max suction temp. threshold
50
-50
50
°C/°F
M
NO
PL1
LOP: min saturated evap. temp. threshold
-50 -50
50
°C/°F
M
NO
PL2
LOP: integral time
0
0
240
s
M
NO
PL3
LOP: alarm delay
0 = function disabled
0
0
240
s
S
NO
cP1
Initial valve position when control starts
30
0
100
%
M
NO
Pdd
Initial valve position maintenance time after defrost
10
0
30
min
S
NO
dSb
Valve position during defrost
0: as defined by the type of defrost
1: forced closed
2 to 100: opening percentage
0
0
100
%
M
NO
PMP
Enable manual expansion valve positioning
0/1 = disabled/enabled
0
0
1
-
S
NO
PMu
Manual valve position
-
0
600
steps
S
NO
PSM
Smooth Lines - enable function
0
0
1
-
S
NO
PLt
Smooth Lines - offset to stop control below set point
2
0
10
°C/°F
S
NO
PHS
Smooth Lines - max superheat offset
15
0
50
K
S
NO
PSd
Derivative time (Smooth Lines)
0
0
100
s
S
NO
PSI
Integral time (Smooth Lines)
120
0
800
s
S
NO
PSP
Proportional gain (Smooth Lines)
5
0
100
-
S
NO
Solenoid/compressor
c0
Delay to enable solenoid/comp. and evap. fans on power-up
0
0
240
min
M
NO
c1
Min time between consecutive compressor starts
0
0
15
min
M
NO
c2
Min compressor OFF time
0
0
15
min
M
NO
c3
Min compressor ON time
0
0
15
min
M
NO
c4
ON time for duty setting operation (Toff = 15 minutes fixed)
0 = compressor/valve always OFF
100 = compressor/valve always ON
0
0
100
min
M
NO
cc
Running time in continuous cycle
0 = Disabled
1
0
15
hours
M
NO
c6
Low temp. alarm bypass time after continuous cycle
60
0
240
min
M
NO
Alarms
A0
High and low temp. alarm reset differential
2
0.1
20
°C/°F
S
YES
A1
Alarm thresholds (AL, AH) relative to the set point St or absolute
0/1 = relative /absolute
0
0
1
-
S
NO
A2
Alarm thresholds (AL2, AH2) relative to the set point St2 or absolute
0/1 = relative /absolute
0
0
1
-
S
NO
A10
Configure solenoid/comp. control during ext. alarm with fixed 15 min OFF time
0 = always OFF
100 = always ON
0
0
14
-
S
NO
A11
Delay time for delayed external alarm
0 = Signal-only alarm
0
0
14
-
S
NO
AA
Assign probe for high (AH) and low (AL) temperature alarms
0: Not configured
1: Air off (Sm)
2: Defrost (Sd)
3: Air on (Sr)
4: Superheated gas (tGS)
5: Reserved
1
0
13
-
S
YES
ENG
0300086EN rel. 1.0 – 04.09.2018
6. Parameter table |
91
Содержание MPXone ACS00CB000010
Страница 2: ......
Страница 6: ......
Страница 17: ...2 6 1 Panel model Fig 2 l ENG MPXone 0300086EN rel 1 0 04 09 2018 2 Installation 17...
Страница 18: ...ENG 2 6 2 DIN rail model Fig 2 m 18 2 Installation MPXone 0300086EN rel 1 0 04 09 2018...
Страница 22: ...ENG DIN Fig 2 s RS485 supervisor network Fig 2 t Fig 2 u 22 2 Installation MPXone 0300086EN rel 1 0 04 09 2018...
Страница 107: ......