Proceed as follows:
1. After starting the configuration software, from the “File” tab open the commissioning file provided by
Carel
2. In the “Target” tab add a "target", i.e. the MPXone controller to communicate with.
3. Set the type of serial communication and change the connection parameters (default for MPXone
baud rate 19200, parity None and 1 stop bit)
4. Select “Connect”.
5. From the “Configurations” tab, select “Add configuration” (e.g. MyConfiguration1).
6. After having created and selected the chosen configuration, select “Copy values to configuration”.
7. The “Configuration value” column will now be populated with the current values on the MPXone
controller. The values can now be modified to create a custom configuration.
8. The recipe created as above can be immediately uploaded to the MPXone controller by selecting
“Apply configuration” or saved for future use by selecting “Export configuration”.
Note:
To create a recipe based on the default values loaded by Carel on the MPXone controller,
simply follow the same procedure as described above, and in step 6 select “Apply default values”
rather than “Copy values to configuration”.
6.2.2 Profiles
Different profiles can be created for displaying the parameters using the configuration software.
Proceed as follows:
1. After starting the configuration software, open the commissioning file provided by Carel;
2. From the “Profiles” tab select “Add profile”;
3. Select “Profiling”';
4. Select the variables to assign to the profile. These will only be the variables that are visible via the
configuration/commissioning software and the Applica app to any M-level user who has the password
for profile MyProfile1.
5. Now, selecting profile MyProfile1, the variables to assign to the profile as read-only can be selected by
checking the check box in the corresponding column;
6. Select “Edit” to set the password associated with the profile;
7. The profile is now ready to be exported; select “Export profile” and upload it to the cloud service
used by the Applica app.
ENG
0300086EN rel. 1.0 – 04.09.2018
6. Parameter table |
95
Содержание MPXone ACS00CB000010
Страница 2: ......
Страница 6: ......
Страница 17: ...2 6 1 Panel model Fig 2 l ENG MPXone 0300086EN rel 1 0 04 09 2018 2 Installation 17...
Страница 18: ...ENG 2 6 2 DIN rail model Fig 2 m 18 2 Installation MPXone 0300086EN rel 1 0 04 09 2018...
Страница 22: ...ENG DIN Fig 2 s RS485 supervisor network Fig 2 t Fig 2 u 22 2 Installation MPXone 0300086EN rel 1 0 04 09 2018...
Страница 107: ......