valve;
l
defrost, dripping, post-dripping are running;
l
the door is open. When the door is opened, the continuous cycle is interrupted. It restarts for
the remaining time when the door is closed.
3. The continuous cycle ends:
l
when deactivating the direct function from the user terminal (see the paragraph "Direct
functions");
l
when reaching the low temperature threshold (AL or AL2 in double thermostat), whichever is
reached first;
l
at the end of the time cc;
l
when the controller is switched off from the supervisor (logical OFF);
l
from the supervisor.
Continuous cycle with shared control status
This operating mode is highlighted on the Master user interface by the corresponding icons on steady;
the Slave controllers ignore the Master control mode and manage the display as normal (solenoid icon on
during the cooling request and off when there is no request).
Defrost priority over continuous cycle
Code
Description
Def Min Max
UOM
User
User
terminal
c7
Defrost priority over continuous cycle
0/1 = No/Yes
0
0
1
-
M
NO
If c7=0 the defrost and continuous cycle are not mutually interruptible (same priority): any defrost or
continuous cycle request remains pending if activated when running the other procedure. If c7=1 the
defrost calls activated when the continuous cycle is running terminate the latter and activate the defrost.
60
| 5. Functions
0300086EN rel. 1.0 – 04.09.2018
Содержание MPXone ACS00CB000010
Страница 2: ......
Страница 6: ......
Страница 17: ...2 6 1 Panel model Fig 2 l ENG MPXone 0300086EN rel 1 0 04 09 2018 2 Installation 17...
Страница 18: ...ENG 2 6 2 DIN rail model Fig 2 m 18 2 Installation MPXone 0300086EN rel 1 0 04 09 2018...
Страница 22: ...ENG DIN Fig 2 s RS485 supervisor network Fig 2 t Fig 2 u 22 2 Installation MPXone 0300086EN rel 1 0 04 09 2018...
Страница 107: ......