6.1
Parameter table
Code
Description
Def Min Max
UOM User
User
terminal
Analogue inputs
/P1
Type of probe, group 1 (S1, S2, S3)
0 = PT1000 Standard Range –50T150 °C
1 = NTC Standard Range –50T90°C
1
0
1
-
S
NO
/P2
Type of probe, group 2 (S4, S5)
1 = NTC Standard Range –50T90°C
2 = 0-5 V
3 = 4-20 mA
2
1
3
-
S
NO
/P3
Type of probe, group 3 (S6)
0 = PT1000 Standard Range –50T150 °C
1 = NTC Standard Range –50T90°C
2 = 0-5 V
3 = 4-20mA
4 = 0-10V
2
0
4
-
S
NO
/FA
Assign air off temp. probe (Sm)
0 = Function disabled
6 = Probe S6
1 = Probe S1
-1 = Serial probe S11
2 = Probe S2
-2 = Serial probe S12
3 = Probe S3
-3 = Serial probe S13
4 = Probe S4
-4 = Serial probe S14
5 = Probe S5
1
-4
6
-
S
NO
/Fb
Assign defrost temperature probe (Sd) - see /FA
2
-4
6
-
S
NO
/Fc
Assign air on temperature probe (Sr) - see /FA
3
-4
6
-
S
NO
/Fd
Assign superheated gas temperature probe (tGS) - see /FA
0
-4
6
-
S
NO
/FE
Assign saturated evaporation pressure/temperature probe (PEu/tEu) - see /FA
0
-4
6
-
S
NO
/FF
Assign defrost temperature probe 2 (Sd2) - see /FA
0
-4
6
-
S
NO
/FG
Assign auxiliary temperature probe 1 (Saux1) - see /FA
0
-4
6
-
S
NO
/FH
Assign auxiliary temperature probe 2 (Saux2) - see /FA
0
-4
6
-
S
NO
/FI
Assign ambient temperature probe (SA) - see /FA
0
-4
6
-
S
NO
/FL
Assign ambient humidity probe (SU) - see /FA
0
-4
6
-
S
NO
/FM
Assign glass temperature probe (Svt) - see /FA
0
-4
6
-
S
NO
/Fn
Assign dewpoint value (SdP) - see /FA
0
-4
6
-
S
NO
/cA
Air off temp. probe (Sm) calibration
0
-20
20
°C/°F
S
NO
/cb
Defrost temp. probe (Sd) calibration
0
-20
20
°C/°F
S
NO
/cc
Air on temp. probe (Sr) calibration
0
-20
20
°C/°F
S
NO
/cd
Superheated gas temperature probe (tGs) calibration
0
-20
20
°C/°F
M
NO
/cE
Saturated evaporation pressure probe (PEu) calibration
0
-20
20
°C/°F
M
NO
/cF
Defrost temp. probe 2 (Sd2) calibration
0
-20
20
°C/°F
S
NO
/cG
Auxiliary temperature probe 1 (Saux1) calibration
0
-20
20
°C/°F
M
NO
/cH
Auxiliary temperature probe 2 (Saux2) calibration
0
-20
20
°C/°F
M
NO
/cI
Ambient temp. probe (SA) calibration
0
-20
20
°C/°F
S
NO
/cL
Ambient humidity probe (SU) calibration
0
-20
20
°C/°F
S
NO
/cM
Glass temperature probe (Svt) calibration
0
-20
20
°C/°F
S
NO
/cn
Dewpoint value (SdP) calibration
0
-20
20
°C/°F
S
NO
/co
Saturated evaporation temperature (tEu) calibration
0
-20
20
°C/°F
M
NO
/UE
Maximum value for saturated evap. pressure/temp. probe (PEu/tEu)
9.3 /LE
200
°C/°F
M
NO
/LE
Minimum value for saturated evap. pressure/temp. probe (PEu/tEu)
0
-1
/UE
°C/°F
M
NO
/UL
Maximum value for ambient humidity probe (SU)
100 /LL
100
%rH
M
NO
/LL
Minimum value for ambient humidity probe (SU)
0
0
/UL
%rH
M
NO
ENG
0300086EN rel. 1.0 – 04.09.2018
6. Parameter table |
85
Содержание MPXone ACS00CB000010
Страница 2: ......
Страница 6: ......
Страница 17: ...2 6 1 Panel model Fig 2 l ENG MPXone 0300086EN rel 1 0 04 09 2018 2 Installation 17...
Страница 18: ...ENG 2 6 2 DIN rail model Fig 2 m 18 2 Installation MPXone 0300086EN rel 1 0 04 09 2018...
Страница 22: ...ENG DIN Fig 2 s RS485 supervisor network Fig 2 t Fig 2 u 22 2 Installation MPXone 0300086EN rel 1 0 04 09 2018...
Страница 107: ......