5. Functions
If the settings made during commissioning are not sufficient to achieve the desired operation, further
(detailed) configuration of the parameters can be performed, as described in the following paragraphs.
The parameters described below can be configured via the configuration software or the "APPLICA" app.
Important:
the information available in Applica may vary according to the password set and the
configuration set by the unit manufacturer, and consequently not all the parameters shown may be
visible or modifiable.
For details on the parameters and the related access levels, see the "Parameter table".
5.1
Inputs and
outputs
MPXone features up to 6 analogue inputs and 5 digital inputs. See the description of the terminals in the
paragraph "Description of the terminals".
The probes (temperature NTC, PT1000, 0-5 Vdc ratiometric and active probes), can be connected to the
analogue inputs, and have been divided into 3 groups, with the same type of probe for each group. See
the parameter table.
Probes
Outputs (Y1, Y2)
Model
Part number
Passive
Active
NTC
(–
50T90°C)
Pt1000
(–
50T150°C)
0 to 5 V
ratiometric
4 to 20
mA
0 to 10 V active
probes
PWM
0 to
10
Vdc
BASIC
S1M0004W0B06
(0/1)
YES
NO
NO
NO
NO
NO
NO
MEDIUM
S1M0006W0B07
(0/1)
YES
YES
YES
YES
YES
YES
YES
S1M0006B0B08
(0/1)
YES
YES
YES
YES
YES
YES
YES
S1M0007N0B11
(0/1)
YES
YES
YES
YES
YES
YES
YES
Important:
observe the maximum allowable current limits on the relays. See the technical
specifications table.
5.1.1 Probes (analogue inputs)
MPXone version
Basic
Medium
Analogue input
S1
S2
S3
S1
S2
S3
S4
S5
S6
Parameter for type of probe
/P1
/P1
/P2
/P3
0 = PT1000 Standard (Range –50T150 °C)
1 =NTC Standard (Range –50T90 °C)
2 = 0-5V ratiometric probe
3 = 4-20 mA input
4 = 0-10V input
Important:
for the maximum current that can be supplied to the ratiometric probes, see the technical
specifications table
Inputs S4, S5 and S6 can be connected to 0-5 V ratiometric pressure probes and active probes with 4-20
mA or 0-10 V output (S6 only). All these probes require the range of measurement to be defined, set by
the relative minimum and maximum parameters for the function associated with the probe. See the
parameter table.
To assign the function to each physical or serial probe, configure parameters /FA, /Fb, ... /Fn. See the
parameter table.
ENG
0300086EN rel. 1.0 – 04.09.2018
5. Functions |
37
Содержание MPXone ACS00CB000010
Страница 2: ......
Страница 6: ......
Страница 17: ...2 6 1 Panel model Fig 2 l ENG MPXone 0300086EN rel 1 0 04 09 2018 2 Installation 17...
Страница 18: ...ENG 2 6 2 DIN rail model Fig 2 m 18 2 Installation MPXone 0300086EN rel 1 0 04 09 2018...
Страница 22: ...ENG DIN Fig 2 s RS485 supervisor network Fig 2 t Fig 2 u 22 2 Installation MPXone 0300086EN rel 1 0 04 09 2018...
Страница 107: ......