5.1.2 Digital inputs
MPXone manages up to 5 physical digital inputs and 1 virtual digital input. See “Installation”.
To associate a physical or virtual input to each available function, set parameters DIA, DIb, ... DIr
parameters to the value relating to the physical or virtual digital input. See the parameter table.
Digital input functions
Contact
Digital input assignment for:
Par.
Open
Closed
immediate external alarm
DIA
Active
Not active
delayed external alarm
DIb
Active
Not active
enable defrost
DIc
Not enabled
Enabled
start defrost
DId
Not active
Active
door switch with stopping control
DIE
Door open
Door closed
remote ON/OFF
DIF
OFF
ON
curtain switch/light
DIG
Day status
Night status
start/stop continuous cycle
DIH
Not active
Active
digital input monitoring
DII
Active
Not active
timed digital input
DIL
Active
Not active
switch to Standby status
DIM
Active
Not active
switch to Clean status
DIn
Active
Not active
change working set
DIo
Set 1
Set 2
door switch without stopping control
DIp
Door open
Door closed
defrost corresponding to digital input status
DIr
Not active
Active
If the opposite logic to the default setting is required, or to correct a wiring error, the logic of the
functions associated with the digital inputs using parameters rIA, rIb, ... rIr can be reversed.
Par.
Description
Def.
UOM
Min
Max
rIA, rIb, ... rIr
Reverse digital input logic
0
-
0
1
Note:
reversing the logic has no effect on the virtual DI
The virtual digital input is a function by which the status of a digital input is broadcast via LAN (RS485)
from Master to Slave. This is useful, for example, when using a switch to change from day to night status
and vice-versa without extra wiring from the Master to the Slaves. The virtual digital input can be set by
the supervisor or by the Master, according to the setting of parameter A9 (set only on the Master).
Code Description
Def Min Max UOM User
User
terminal
A9
Select digital input broadcast from Master to Slaves (only on
Master)
0 = from supervisor
3 = Digital input 3 (ID3)
1 = Digital input 1 (ID1)
4 = Digital input 4 (ID4)
2 = Digital input 2 (ID2)
5 = Digital input 5 (ID5)
0
0
5
-
S
NO
Setting parameters DIA, DIb, ... DIr to -1 allows the virtual digital input to be selected on the Slave as an
input. If needed, different functions can be configured on the Slaves, meaning when the status of the
contact on the Master changes, different functions are activated on the Slaves.
Par.
Description
Def.
UOM
Min
Max
DIA, DIb, ... DIr
Assign digital input function
...
- 1: serial digital input
0
-
-1
5
ENG
0300086EN rel. 1.0 – 04.09.2018
5. Functions |
41
Содержание MPXone ACS00CB000010
Страница 2: ......
Страница 6: ......
Страница 17: ...2 6 1 Panel model Fig 2 l ENG MPXone 0300086EN rel 1 0 04 09 2018 2 Installation 17...
Страница 18: ...ENG 2 6 2 DIN rail model Fig 2 m 18 2 Installation MPXone 0300086EN rel 1 0 04 09 2018...
Страница 22: ...ENG DIN Fig 2 s RS485 supervisor network Fig 2 t Fig 2 u 22 2 Installation MPXone 0300086EN rel 1 0 04 09 2018...
Страница 107: ......