CDE360 Vector Control AC Drive Chapter 6 Parameters Description
Group E5: PID
E5.00
①
Range: 0~1
Default: 0
PID engineering
unit
This parameter determines the unit of PID regulator.
0: Percentage(%) 1: Pressure(MPa)
The following parameters’ unit is determined by
E5.00
.
E5.05
(PID digital setting)
E5.33
(Upper limit of PID
feedback detection)
E5.03
(Minimum setting of PID
engineering unit)
E5.34
(Lower limit of PID
feedback detection)
E5.02
(Maximum setting of PID
engineering unit)
E5.36
(Wake up level)
E5.16
(PID parameter
switchover deviation 1)
E5.39
(Sleep level)
E5.17
(PID parameter
switchover deviation 2)
A0.20
(PID reference)
E5.26
(PID deviation limit)
A0.21
(PID feedback)
Note:
The above 12 parameters’ unit will change immediately according to
E5.00
.
E5.01
Range: 0~3
Default: 1
PID engineering
unit resolution
0: No decimal
1: One decimal
2: Two decimal
3: Three decimal
This parameter determined the resolution of the following parameter:
E5.05
(PID digital setting)
E5.33
(Upper limit of PID
feedback detection)
E5.03
(Minimum setting of PID
engineering unit)
E5.34
(Lower limit of PID
feedback detection)
E5.02
(Maximum setting of PID
engineering unit)
E5.36
(Wake up level)
E5.16
(PID parameter
Switchover deviation 1)
E5.39
(Sleep level)
E5.17
(PID parameter
switchover deviation 2)
A0.20
(PID reference)
E5.26
(PID deviation limit)
A0.21
(PID feedback)
Note:
The resolution of above 12 parameters will change immediately
according to
E5.01
.
The PID engineering unit is convenient for customer using.Different engineering unit will be
converted to percentage in the AC drive PID regulator.The percentage value of final PID setting and
feedback will be again converted to the real value with engineering unit,and then shown to
customers.