CDE360 Vector Control AC Drive Chapter 6 Parameters Description
When d3.05 is set to 4 (Running fre windows), speed limit mode is shown by
Fig6-D11:
Running frequency
Negative window
t
Speed control
is active
Positive window
Speed control
is active
Torque control
is active
Speed
Figure 6- 30 d3.05=4 Running fre windows
When d3.05 is set to 5 (0Hz to running frequency), speed limit mode is shown byFig6-D12:
Running frequency
t
Speed control
is active
Speed control
is active
Torque control
is active
Speed
Figure 6- 31 d3.05=5 0Hz to running frequency
d3.12
Range: 0.0 ~ 100.0
Default: 0.0
Static torque
compensation
Unit: %
To overcome the static friction, static torque compensation is helpful.
100% of the setting corresponds to rated motor torque.
d3.13
Range: 0.0 ~ 100.0
Default: 0.0
Dynamic torque
compensation
Unit: %
To overcome the dynamic friction, dynamic torque compensation is
helpful. 100% of the setting corresponds to rated motor torque.
d3.14
Range: 0.0 ~ 100.0
Default: 0.0
Inertia torque
compensation
Unit: %
To overcome the system inertia, inertia torque compensation is helpful.
100% of the setting corresponds to rated motor torque.
d3.15
Range: 0.00 ~ 650.00
Default: 2.00
Torque
acceleration time
Unit: Sec
This defines the time required for actual torque reference to change from