CDE360 Vector Control AC Drive Chapter 6 Parameters Description
-
96
-
from 0 Hz to
E4.09
, please see the T1 in the following figure.
b0.05
Deceleration
time 1
Range: 0.1~6000.0
Default: Model dependent
Unit: Sec
Deceleration time indicates the time required by the drive to decelerate
from
E4.09
to 0 Hz, please see the T2 in the following figure.
Output freq
E4.09
Referency freq
Acc time of actually
Acc time of setting
T1
T2
Dec time of actually
Dec time of setting
Figure 6- 3 Acc/Dec time map
b0.06
①
Range: 0.1~999.9
Default: Model dependent
Motor rated
power
Unit: kW
The default value of motor rated power is the same with AC drive rated
power(G type).
For example:
If the AC drive type is 4T-3R7G/5R5L, then the default value of motor
rated power is 3.7kW.
If the AC drive type is 4T-5R5G/7R5L, then the default value of motor
rated power is 5.5kW.
b0.07
①
Range: 1~2000
Default: Model dependent
Motor rated
voltage
Unit: V
The default value of motor rated voltage and AC drive voltage level are
consistent.
b0.08
①
Motor rated
current
Range:
0.01~655.35(Drive power ≤ 55kW)
0.1~6553.5(Drive power ≥ 75kW)
Default: Model dependent
Unit: A
The default value of motor rated current matches with motor rated power.
When you modified b0.06(motor rated power), motor rated current default
value will be changed.
b0.09
①
Range: 10.00~
b0.00
Default: 50.00
Motor rated
frequency
Unit: Hz
Please set according to the motor nameplate data.