CDE360 Vector Control AC Drive Chapter 6 Parameters Description
C1.06
Range: 0~45
Default: 0
T3 Function
Defines the functions of rely T3, same as C1.01.
C1.07
Range: 0~45
Default: 0
T4 Function
Defines the functions of rely T4, same as C1.01.
C1.08
Range: 0~45
Default: 0
T5 Function
Defines the functions of rely T5, same as C1.01.
C1.09
Range: 0~45
Default: 0
T6 Function
Defines the functions of rely T6, same as C1.01.
C1.10
Range: 000~111
Default: 000
Y terminals valid
state logic
0: Positive logic; When valid output ON signal, when invalid output OFF
signal.
1: Negative logic; When valid output OFF signal, when invalid output ON
signal.
Unit:
Y1
Tens:
Y2
Hundreds:
Y3
C1.11
Range: 0000~1111
Default: 0000
T1~T4 terminals
valid state logic
Define the relays T1~T4 valid state, same as C1.10.
Unit:
T1
Tens:
T2
Hundreds:
T3
Thousands:
T4
C1.12
Range: 00~11
Default: 00
T5~T6 terminals
valid sate logic
Define the relays T5~T6 valid state, same as C1.10.
Unit:
T5
Tens:
T6
Note:
0: Positive logic said digital output terminal and the common end(COM) connected
state. Connect means ON state, disconnect means OFF state.
1: Positive logic said digital output terminal and the common end(COM) connected
state. Connect means OFF state, disconnect means ON state.
C1.13
Range: 0.0~3000.0
Default: 0.0
Y1 output delay
time
Unit: Sec
Define the output delay time of output switch terminal Y1.
Represents the delay time of output function state changes to the actual
output changes, this is can increase the stability of the output signal, as
the following figure shown.