CDE360 Vector Control AC Drive Chapter 6 Parameters Description
-
98
-
C0.03
X3 function
-
48: Motor 1# interlock input
C0.04
X4 function
-
49: Motor 2# interlock input
C0.18
UP/DOWN adjustment
selection
2: PID reference
2: PID reference
C1.04
T1 function
-
40: Motor 1# control output
C1.05
T2 function
38: PID sleep status indication
41: Motor 2# control output
C2.04
AI curve1 minimum
input
2.00V
2.00V
E5.00
①
PID engineering unit
1: Pressure(MPa)
1: Pressure(MPa)
E5.01
PID engineering unit
resolution
2: Two decimals
2: Two decimals
E5.02
Maximum setting of
PID engineering unit
1.00 MPa
1.00 MPa
E5.05
PID digital setting
0.50 MPa
0.50 MPa
E5.26
PID deviation limit
1.0%
1.0%
E5.36
Wake up level
50.0%
50.0%
E5.37
Wake up delay time
1.0 Sec
1.0 Sec
E5.40
Sleep frequency
22.00 Hz
22.00 Hz
E5.41
Sleep delay time
1.0 Sec
1.0 Sec
E6.00
Multi-pump control
mode
-
4: Frequency pump
circulation,Support auto change
E6.01
Number of motors
-
2
E6.05
Interlock functions
-
01: Interlock enabled,decided by
X terminals
H0.01
LED display running
parameters 1
24715(1+2+8+128+8192+16384)
24715(1+2+8+128+8192+16384)
H0.02
LED display running
parameters 2
-
1024
H0.03
LED display stop
parameters
787(1+2+16+256+512)
787(1+2+16+256+512)