CDE360 Vector Control AC Drive Chapter 6 Parameters Description
C0.06
①
Range: 0~58
Default: 0
X6 function
Same as
C0.01
.
C0.07
①
Range: 0~58
Default: 0
X7 function
Same as
C0.01
.
C0.08
①
Range: 0~58
Default: 0
X8 function
Same as
C0.01
.
C0.09
①
Range: 0~58
Default: 0
X9 function
Same as
C0.01
.
C0.10
①
Range: 0~58
Default: 0
X10 function
Same as
C0.01
.
C0.11
Range: 0000~1111
Default: 0000
X1~X4 terminal
logic
Used to define X1~X4 terminal logically valid state, Set according to LED
bits(unit,tens,hundreds,thousands): Unit corresponding to X1,Tens
corresponding to X2,Hundreds corresponding to X3,Thousands
corresponding to X4.
The definition for each bit:
0: Closed effective. If the 24V connect to CMX, when the terminal and COM
short connection indicate effectively.
1: Disconnect effective. If the 24V connect to CMX, when the terminal and
COM disconnected indicate effectively.
C0.12
Range: 0000~1111
Default: 0000
X5~X8 terminal
logic
Used to define X5~X8 terminal logically valid state, Set according to LED
bits(unit,tens,hundreds,thousands): Unit corresponding to X5, Tens
corresponding to X6, Hundreds corresponding to X7, Thousands
corresponding to X8.
C0.13
Range: 00~11
Default: 00
X9~X10 terminal
logic
Used to define X9~X10 terminal logically valid state, Set according to LED
bits(unit,tens,hundreds,thousands): Unit corresponding to X9,Tens
corresponding to X10, Each bit definition is same as C0.11
C0.14
Range: 0.0~3000.0
Default: 0.0
X1 terminal delay
time
Unit: Sec
Delayed response time to set the X1 terminal of the input signal