CDE360 Vector Control AC Drive Chapter 6 Parameters Description
Group E2: Multi-Reference
The AC drive multi-reference has many functions. Besides multi-speed, it can be used as the
setting source of the V/F separated voltage source and setting source of process PID.
The multi-reference is frequency value and ranges from
-b0.00
to
b0.00
.
As frequency source, it does not require conversion.As others, it needs to be changed to a
percentage relative to
b0.00
(Max frequency).
Multi-reference can be switched over based on different states of X terminals. For details, see
the descriptions of
Group C0
.
E2.00
Range: 0~6
Default: 0
Reference 0
source
0: Set by
E2.01
1: Set by
b2.01
,modified via UP/DOWN
2: AI1 3: AI2 4: AI3 5: X6/FI 6: PID
It determines the setting channel of reference 0. You can perform
convenient switchover between the setting channels. When
multi-reference or simple PLC is used as frequency source, the
switchover between two frequency sources can be realized easily.
E2.01
Range: -
b0.00
~
b0.00
Default: 0.00
Reference 0
Unit: Hz
Multi-reference 0 set frequency.
The descriptions of
Reference 1
to
Reference 15
are the same with
Reference 0
(
E2.01
).
E2.02
Reference 1
E2.03
Reference 2
E2.04
Reference 3
E2.05
Reference 4
E2.06
Reference 5
E2.07
Reference 6
E2.08
Reference 7
E2.09
Reference 8
E2.10
Reference 9
E2.11
Reference 10
E2.12
Reference 11
E2.13
Reference 12
E2.14
Reference 13
E2.15
Reference 14
E2.16
Reference 15