Section 8. Operation
392
Tips for writing a control program:
•
Short Cut
programming wizard has provisions for simple on/off control.
•
PID control can be done with the CR800.
Control decisions can be based on time, an event, or a measured condition.
Example:
In the case of a cell modem, control is based on time. The modem requires 12 Vdc
power, so connect its power wire to the CR800
SW12V
terminal. The following
code snip turns the modem on for ten minutes at the top of the hour using the
TimeIntoInterval()
instruction embedded in an
If
/
Then
logic statement:
If
TimeIntoInterval
( 0,60,Min) Then
PortSet
(9,1)
'Port “9” is
the SW12V Port. Turn phone on.
If
TimeIntoInterval
(10,60,Min) Then
PortSet
(9,0)
'Turn phone
off.
TimeIsBetween()
returns
TRUE
if the CR800 real-time clock falls within the
specified range; otherwise, the function returns
FALSE
. Like
TimeIntoInterval()
,
TimeIsBetween()
is often embedded in an
If
/
Then
logic
statement, as shown in the following code snip.
If
TimeIsBetween
(0,10,60,Min)
Then
SW12
(1)
'Turn phone on.
Else
SW12
(0)
'Turn phone off.
EndIf
TimeIsBetween()
returns
TRUE
for the entire interval specified whereas
TimeIntoInterval()
returns
TRUE
only for the one scan that matches the interval
specified.
For example, using the preceding code snips, if the CRBasic program is sent to
the datalogger at one minute past the hour, the
TimeIsBetween()
instruction will
evaluate as
TRUE
on its first scan. The
TimeIntoInterval()
instruction will
evaluate as
TRUE
at the top of the next hour (59 minutes later).
•
Note
START is inclusive and STOP is exclusive in the range of time
that will return a TRUE result. For example:
TimeIsBetween
(0,10,60,Min) will return TRUE at 8:00:00.00 and
FALSE at 08:10:00.00.
8.3.1 Terminals Configured for Control
C
terminals can be configured as output ports to set low (0 Vdc, turn off) or high
(5 Vdc, turn on) using the
PortSet()
or
WriteIO()
instructions. Port
C4
can be
configured for pulse width modulation with a maximum period of 36.4 s. A
terminal configured for digital I/O is normally used to operate an external relay-
driver circuit because the port itself has limited drive capacity.Current sourcing
for drive capcitiy is determined by the 5 Vdc supply and a 330 Ω output
resistance. It is expressed as:
Содержание CR800 Series
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 32: ......
Страница 34: ......
Страница 54: ......
Страница 92: ......
Страница 190: ...Section 7 Installation 190 FIGURE 40 Running Average Frequency Response FIGURE 41 Running Average Signal Attenuation ...
Страница 310: ......
Страница 446: ...Section 8 Operation 446 8 11 2 Data Display FIGURE 100 CR1000KD Displaying Data ...
Страница 448: ...Section 8 Operation 448 FIGURE 102 CR1000KD Real Time Custom ...
Страница 449: ...Section 8 Operation 449 8 11 2 3 Final Storage Data FIGURE 103 CR1000KD Final Storage Data ...
Страница 450: ...Section 8 Operation 450 8 11 3 Run Stop Program FIGURE 104 CR1000KD Run Stop Program ...
Страница 452: ...Section 8 Operation 452 FIGURE 106 CR1000KD File Edit ...
Страница 456: ......
Страница 462: ......
Страница 523: ...Section 11 Glossary 523 FIGURE 116 Relationships of Accuracy Precision and Resolution ...
Страница 524: ......
Страница 526: ......
Страница 556: ......
Страница 558: ......
Страница 560: ......
Страница 597: ......