Section 10. Troubleshooting
472
Warning Message Examples
Message
Meaning
Warning: COM310 word list
cannot be a variable.
The
Phrases
parameter of the
VoicePhrases()
instruction was assigned a
variable name instead of the required string of comma-separated words
from the Voice.TXT file.
Warning: EndIf never reached at
runtime.
Program will never execute the
EndIf
instruction. In this case, the cause is
a
Scan()
with a
Count
parameter of 0, which creates an infinite loop within
the program logic.
Warning: Internal Data Storage
Memory was re-initialized.
Sending a new program has caused final-memory to be re-allocated.
Previous data are no longer accessible.
Warning: Machine self-
calibration failed.
Indicates a problem with the analog measurement hardware during the auto
self-calibration. An invalid external sensor signal applying a voltage
beyond the internal
±
8 Vdc supplies on a voltage input can induce this
error. Removing the offending signal and powering up the logger will
initiate a new auto self-calibration. If the error does not occur on power-up,
the problem is corrected. If no invalid external signals are present and / or
auto self-calibration fails again on power-up, the CR800 should be repaired
by a qualified technician.
Warning: Slow Seq 1, Scan 1,
will skip scans if running with
Scan 1
SlowSequence
scan rate is <= main scan rate. This will cause skipped
scans on the
SlowSequence
.
Warning: Table [tablename] is
declared but never called.
No data will be stored in [tablename] because there is no
CallTable()
instruction in the program that references that table.
Warning: Units:
a_units_name_that_is_more_than
_38_chara... too long will be
truncated to 38 chars.
The label assigned with the
Units
argument is too long and will be
truncated to the maximum allowed length.
Warning: Voice word TEH is not
in Voice.TXT file
The misspelled word TEH in the
VoiceSpeak()
instruction is not found in
Voice.TXT file and will not be spoken by the voice modem.
Voltage calibration failure!
Loose wire probably of a bridge sensor such as a wind vane or pressure
transducer
10.5.4.2 SkippedScan
Skipped scans are caused by long programs with short scan intervals, multiple
Scan()
/
NextScan
instructions outside a
SubScan()
or
SlowSequence
, frame
errors, or by other operations that occupy the processor at scan start time.
Occasional skipped scans may be acceptable but should be avoided. Skipped
scans may compromise frequency measurements made on terminals configured
for pulse input. The error occurs because counts from a scan and subsequent
Содержание CR800 Series
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 32: ......
Страница 34: ......
Страница 54: ......
Страница 92: ......
Страница 190: ...Section 7 Installation 190 FIGURE 40 Running Average Frequency Response FIGURE 41 Running Average Signal Attenuation ...
Страница 310: ......
Страница 446: ...Section 8 Operation 446 8 11 2 Data Display FIGURE 100 CR1000KD Displaying Data ...
Страница 448: ...Section 8 Operation 448 FIGURE 102 CR1000KD Real Time Custom ...
Страница 449: ...Section 8 Operation 449 8 11 2 3 Final Storage Data FIGURE 103 CR1000KD Final Storage Data ...
Страница 450: ...Section 8 Operation 450 8 11 3 Run Stop Program FIGURE 104 CR1000KD Run Stop Program ...
Страница 452: ...Section 8 Operation 452 FIGURE 106 CR1000KD File Edit ...
Страница 456: ......
Страница 462: ......
Страница 523: ...Section 11 Glossary 523 FIGURE 116 Relationships of Accuracy Precision and Resolution ...
Страница 524: ......
Страница 526: ......
Страница 556: ......
Страница 558: ......
Страница 560: ......
Страница 597: ......