7.7.11 Field Calibration — Details
Related Topics:
•
Field Calibration — Overview
(p. 75)
•
Field Calibration — Details
(p. 214)
Calibration increases accuracy of a sensor by adjusting or correcting its output to
match independently verified quantities. Adjusting a sensor output signal is
preferred, but not always possible or practical. By using the
FieldCal()
or
FieldCalStrain()
instruction, a linear sensor output can be corrected in the CR800
after the measurement by adjusting the multiplier and offset.
When included in the CRBasic program,
FieldCal()
and
FieldCalStrain()
can be
used through a datalogger support software
calibration wizard
(p. 491).
Help for
using the wizard is available in the software.
A more arcane procedure that does not require a PC can be executed though the
CR1000KD Keyboard / Displayor. If you do not have a keyboard, the same
procedure can be done in a
numeric monitor
(p. 506).
Numeric monitor screen
captures are used in the following procedures. Running through these procedures
will give you a foundation for how field calibration works, but use of the
calibration wizard for routine work is recommended.
More detail is available in
CRBasic Editor Help
.
7.7.11.1 Field Calibration CAL Files
Calibration data are stored automatically, usually on the CR800 CPU: drive, in
CAL (.cal) files. These data become the source for calibration factors when
requested by the
LoadFieldCal()
instruction. A file is created automatically on
the same CR800 memory drive and given the same name as the program that
creates and uses it. For example, the CRBasic program file CPU:MyProg.cr8
generates the CAL file CPU:MyProg.cal.
CAL files are created if a program using
FieldCal()
or
FieldCalStrain()
does not
find an existing, compatible CAL file. Files are updated with each successful
calibration with new calibration factors factors. A calibration history is recorded
only if the CRBasic program creates a
data table
(p. 495)
with the
SampleFieldCal()
instruction.
Note
CAL files created by
FieldCal()
and
FieldCalStrain()
differ from
files created by the
CalFile()
instruction See
File Management in CR800
Memory
(p. 416).
Содержание CR800 Series
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 32: ......
Страница 34: ......
Страница 54: ......
Страница 92: ......
Страница 190: ...Section 7 Installation 190 FIGURE 40 Running Average Frequency Response FIGURE 41 Running Average Signal Attenuation ...
Страница 310: ......
Страница 446: ...Section 8 Operation 446 8 11 2 Data Display FIGURE 100 CR1000KD Displaying Data ...
Страница 448: ...Section 8 Operation 448 FIGURE 102 CR1000KD Real Time Custom ...
Страница 449: ...Section 8 Operation 449 8 11 2 3 Final Storage Data FIGURE 103 CR1000KD Final Storage Data ...
Страница 450: ...Section 8 Operation 450 8 11 3 Run Stop Program FIGURE 104 CR1000KD Run Stop Program ...
Страница 452: ...Section 8 Operation 452 FIGURE 106 CR1000KD File Edit ...
Страница 456: ......
Страница 462: ......
Страница 523: ...Section 11 Glossary 523 FIGURE 116 Relationships of Accuracy Precision and Resolution ...
Страница 524: ......
Страница 526: ......
Страница 556: ......
Страница 558: ......
Страница 560: ......
Страница 597: ......