![Campbell CR800 Series Скачать руководство пользователя страница 442](http://html1.mh-extra.com/html/campbell/cr800-series/cr800-series_operators-manual_489099442.webp)
Section 8. Operation
442
Q: Can I make some registers read-only and other registers writable?
A: Yes. By default all registers mapped to
ModbusSlave()
are writable. You may
make individual registers read-only with the
ReadOnly()
instruction in the
CR800 CRBasic program.
The following example demonstrates how to report data by Modbus but not allow
a Modbus client to change register or coil values in the Modbus host:
•
Var
can be viewed and changed
•
Reg()
and
Coil()
can only be viewed
•
The CRBasic program can read from and write to all variables
Public
Var
Public
Reg(4), Coil(4) as Boolean
ReadOnly
Reg, Coil
BeginProg
'setup modbus tcp/ip slave
'readonly instruction above makes reg and coil read only / not
writable
ModbusSlave
(502,0,1,Reg,Coil,2)
Scan
(5,Sec,0,0)
var = var + 1 ' increment var
MBReg() = MBReg() + 0.1
'increment all the registers
MBCoil() = (NOT MBCoil())
'toggle all the coils
NextScan
EndProg
8.10.3.6 Modbus Over RS-232 7/E/1
Q: Can Modbus be used over an RS-232 link, 7 data bits, even parity, one stop
bit?
A: Yes. Precede
ModBusMaster()
/
ModBusSlave()
with
SerialOpen()
and set
the numeric format of the COM port with any of the available formats, including
the option of 7 data bits, even parity.
SerialOpen()
and
ModBusMaster()
can
be used once and placed before
Scan()
.
8.10.3.7 Converting Modbus 16-Bit to 32-Bit Longs
Concatenation of two Modbus long 16-bit variables to one Modbus long 32
bit number is shown in the following example:
Содержание CR800 Series
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 32: ......
Страница 34: ......
Страница 54: ......
Страница 92: ......
Страница 190: ...Section 7 Installation 190 FIGURE 40 Running Average Frequency Response FIGURE 41 Running Average Signal Attenuation ...
Страница 310: ......
Страница 446: ...Section 8 Operation 446 8 11 2 Data Display FIGURE 100 CR1000KD Displaying Data ...
Страница 448: ...Section 8 Operation 448 FIGURE 102 CR1000KD Real Time Custom ...
Страница 449: ...Section 8 Operation 449 8 11 2 3 Final Storage Data FIGURE 103 CR1000KD Final Storage Data ...
Страница 450: ...Section 8 Operation 450 8 11 3 Run Stop Program FIGURE 104 CR1000KD Run Stop Program ...
Страница 452: ...Section 8 Operation 452 FIGURE 106 CR1000KD File Edit ...
Страница 456: ......
Страница 462: ......
Страница 523: ...Section 11 Glossary 523 FIGURE 116 Relationships of Accuracy Precision and Resolution ...
Страница 524: ......
Страница 526: ......
Страница 556: ......
Страница 558: ......
Страница 560: ......
Страница 597: ......