Appendix B. Status, Settings, and Data Table Information (Status/Settings/DTI)
Table 180.
Status/Settings/DTI: P
Keyword
Alias,
Access,
Description
Read/Write,
DataType,
Units
Default
Value
Normal
Range
PakBusAddress
Settings Editor:
PakBus Address
Keyboard:
Settings (General)
≈ line 5
CRBasic:
variable = settings.keyword
;
SetSettings()
PakBus address for this CR1000. Assign a unique
address if this CR1000 is to be placed in a PakBus
network. Addresses 1 to 4094 are valid, but those ≥
4000 are usually reserved for datalogger support
software
(p. 95).
Many Campbell Scientific devices,
including dataloggers, default to address 1.
read/write
LONG
1
1 to 3999
PakBusEncryptionKey
Settings Editor:
PakBus Encryption Key
Keyboard:
Settings (General)
≈ line 9
CRBasic:
variable = settings.keyword
;
SetSettings()
read/write
STRING
none
0 to 63
characters
PakBusNodes
Obsolete. Replaced by/aliased to
CommsMemAlloc
PakBusPort
Settings Editor:
PakBus/TCP Service Port
Keyboard:
Settings (TCP/IP)
≈ line 16
CRBasic:
variable = settings.keyword
;
SetSettings()
Replaces old
TCPPort
setting. Effective only if the
PPP service is enabled using a PPP-compatible
network link
(p. 652).
Specifies the TCP service port
for PakBus communications with the CR1000.
Unless firewall issues exist, this setting probably
does not need to be changed from its default value.
read only
LONG
6785
0 to 65535
PakBusRoutes
Settings Editor:
Routes
Keyboard:
Status Table
≈ line 53
CRBasic:
variable = status.keyword
Lists routes or router neighbors known to the
CR1000 at the time the setting was read. Each route
is represented by four components separated by
commas and enclosed in parentheses:
(port, via neighbor adr, pakbus adr,
response time)
See section
PakBusRoutes
(p. 405).
read only
STRING
(1, 4089,
4089, 1000)
?
PakBusTCPClients
Settings Editor:
PakBus/TCP Clients
Alias:
PakBus/TCP Client Connections
Keyboard:
Settings (TCP/IP)
≈ line 33
CRBasic:
variable = settings.keyword
;
SetSettings()
Up to four addresses specifying outgoing
PakBus/TCP connections that the datalogger is to
maintain. Formal syntax of the setting:
TCP Connections := 4{ address_pair }.
address_pair := "(" address "," tcp-port ")".
address := domain-name | ip-address.
Example of two connections:
(192.168.4.203, 6785)
(JOHN_DOE.server.com, 6785)
read/write
STRING
( , 0)
n/a
623
Содержание CR1000
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 32: ......
Страница 36: ......
Страница 38: ......
Страница 40: ......
Страница 60: ...Section 4 System Quickstart Figure 16 PC200W View Line Graph 60 ...
Страница 96: ......
Страница 98: ...98 ...
Страница 302: ......
Страница 350: ...Section 8 Operation Figure 91 Pulse Sensor Output Signal Types Figure 92 Switch Closure Pulse Sensor 350 ...
Страница 453: ...Section 8 Operation Figure 115 Using the Keyboard Display 453 ...
Страница 454: ...Section 8 Operation 8 8 1 Data Display Figure 116 Displaying Data with the Keyboard Display 454 ...
Страница 456: ...Section 8 Operation Figure 118 Real Time Custom 456 ...
Страница 457: ...Section 8 Operation 8 8 1 3 Final Memory Tables Figure 119 Final Memory Tables 457 ...
Страница 458: ...Section 8 Operation 8 8 2 Run Stop Program Figure 120 Run Stop Program 458 ...
Страница 460: ...Section 8 Operation Figure 122 File Edit 460 ...
Страница 461: ...Section 8 Operation 8 8 4 PCCard Memory Card Display Figure 123 PCCard CF Card Display 461 ...
Страница 478: ......
Страница 506: ......
Страница 536: ......
Страница 636: ......
Страница 642: ......
Страница 644: ......
Страница 676: ......
Страница 677: ......