Section 7. Installation
36 Hz / 50 Hz = 0.72
SIN(0.72π) / (0.72π) = 0.34.
So, the recorded amplitude was about 1/3 of the input-signal amplitude. A
CRBasic program was written with variables
Accel2
and
Accel2RA
. The
raw measurement was stored in
Accel2
.
Accel2RA
held the result of
performing a running average on the
Accel2
. Both values were stored at a
rate of 500 Hz. Figure
Running-Average Signal Attenuation
(p. 195)
shows the
two variables plotted to illustrate the attenuation. The running-average value
has the lower amplitude.
The resultant delay, D
r
, is calculated as follows:
D
r
= (scan rate) • (N–1)/2 = 2 ms (10–1)/2
= 9 ms
D
r
is about 1/3 of the input-signal period.
Figure 52. Running-Average Frequency Response
194
Содержание CR1000
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 32: ......
Страница 36: ......
Страница 38: ......
Страница 40: ......
Страница 60: ...Section 4 System Quickstart Figure 16 PC200W View Line Graph 60 ...
Страница 96: ......
Страница 98: ...98 ...
Страница 302: ......
Страница 350: ...Section 8 Operation Figure 91 Pulse Sensor Output Signal Types Figure 92 Switch Closure Pulse Sensor 350 ...
Страница 453: ...Section 8 Operation Figure 115 Using the Keyboard Display 453 ...
Страница 454: ...Section 8 Operation 8 8 1 Data Display Figure 116 Displaying Data with the Keyboard Display 454 ...
Страница 456: ...Section 8 Operation Figure 118 Real Time Custom 456 ...
Страница 457: ...Section 8 Operation 8 8 1 3 Final Memory Tables Figure 119 Final Memory Tables 457 ...
Страница 458: ...Section 8 Operation 8 8 2 Run Stop Program Figure 120 Run Stop Program 458 ...
Страница 460: ...Section 8 Operation Figure 122 File Edit 460 ...
Страница 461: ...Section 8 Operation 8 8 4 PCCard Memory Card Display Figure 123 PCCard CF Card Display 461 ...
Страница 478: ......
Страница 506: ......
Страница 536: ......
Страница 636: ......
Страница 642: ......
Страница 644: ......
Страница 676: ......
Страница 677: ......