35. Place on the fifth fire clay ring with the connection
hole and adjust the rotary chimney direction by
turning.
36. Prepare pipe expander. Please wrap the sealing
fleece around the Ø 150 mm and cut to fit.
37. Now fit the pipe expander, Ø 150 mm to Ø 160 mm
with the sealing fleece in the connection hole.
38. Place on final fire clay ring with connecting hole.
18.2 Continuation of installation of S21 GO-Line with wall connection
39. Remove all components (with the exception of the
floor panel) again while marking and drilling the con-
nections (fireplace connection)
Connections:
Flue gas connector Ø 160 mm:
Connection height from upper edge of finished floor
(OKFF) to centre of connection = 1807 mm
External air connection Ø 125 mm:
Connection height from upper edge of finished floor
(OKFF) to centre of connection = 165 mm
Wall distance to rear wall = 100 mm
180
7 mm
Outside air
connection
165 mm
The further installation steps differ for the S21 GO-Line heat storage system wall and ceiling connection
variant and are described in the following chapters.