Figure 9.b: Piping Method #1 - indirect Water Heater loop Piping (shaded)
TablE 9.: PiPE anD CirCulaTOr siZing FOr bOilEr lOOP
BOILER
MODEL
(a)
(b)
(c)
(d)
(e)
PIPE SIZE
(in NPT)
FLOW
(GPM)
TEMP RISE
(F)
CIRCULATOR
MODEL
BOILER LOOP
MAX EQUIVALENT
LENGTH (ft)
FCM070
1
6.0
22
Taco 007
55
FCM070
1
6.0
22
Taco 008
145
FCM090
1
8.0
21
Taco 0014
90
FCM090
1
8.0
21
Taco 0013 (
Note #1
)
230
FCM120
1
8.0
29
Taco 0014
111
FCM120
1
9.0
25
Taco 0014
61
FCM120
1
12.0
19
Taco 0013 (
Note #1
)
28
NOTE
: 1) Use isolation relay between Taco 0013 and FCM - see Figure 10.3
Содержание FREEDOM
Страница 8: ...8 Figure 1 Wall Mounting Hole locations ...
Страница 9: ...9 Figure 5 2 Boiler Mounting Hardware ...
Страница 11: ...11 Figure 6 1 Boiler Installed In A Confined Space Ventilation Air From Inside ...
Страница 24: ...24 Figure 7 20 Installation of Reducing Elbow on Concentric Boiler Collar Figure 7 21 Dimension L ...
Страница 34: ...34 Figure 7 35b Cutting Vertical Terminal Figure 7 35c Completing Vertical Terminal Installation ...
Страница 42: ...42 FIGURE 7 51 CONDENSATE PIPING ARRANGEMENT ...
Страница 55: ...55 Figure 10 1 Wiring Connections Diagram ...
Страница 56: ...56 Figure 10 2 Ladder Diagram ...
Страница 57: ...57 Figure 10 3 Wiring of Isolation Relay for Control of Two Heating Circulators ...
Страница 60: ...60 FCM Series Lighting and Operating Instructions ...
Страница 66: ...66 FIGURE 12 2 BASIC MENU TREE ...
Страница 75: ...75 ...
Страница 77: ...77 ...
Страница 79: ...79 ...
Страница 80: ...80 ...
Страница 81: ...81 ...
Страница 83: ...83 150 151 152 153 154 155 ...
Страница 84: ...84 156 157 158 159 160 161 ...
Страница 85: ...85 162 ...