193
Supplementary information
Type 8792, 8793 REV.2
Setting the parameters according to Chien, Hrones and Reswick
Setting the parameters
Controller type for aperiodic control process
(0% overshoot)
for control process
with 20% overshoot
Reference
Malfunction
Reference
Malfunction
P controller
Kp = 0.3 ·
Tg
Tu · Ks
Kp = 0.3 ·
Tg
Tu · Ks
Kp =
0.7 ·
Tg
Tu · Ks
Kp = 0.7·
Tg
Tu · Ks
PI controller
Kp = 0.35 ·
Tg
Tu · Ks
Kp = 0.6 ·
Tg
Tu · Ks
Kp = 0.6 ·
Tg
Tu · Ks
Kp = 0.7·
Tg
Tu · Ks
Tn = 1.2 · Tg
Tn = 4 · Tu
Tn = Tg
Tn = 2.3 · Tu
PID controller
Kp = 0.6 ·
Tg
Tu · Ks
Kp = 0.95 ·
Tg
Tu · Ks
Kp = 0.95 ·
Tg
Tu · Ks
Kp =
1.2 ·
Tg
Tu · Ks
Tn = Tg
Tn = 2.4 · Tu
Tn = 1.35 · Tg
Tn = 2 · Tu
T v = 0.5 · Tu
T v = 0.42 · Tu
T v = 0.47 · Tu
T v = 0.42 · Tu
Table 74:
Setting the parameters according to Chien, Hrones and Reswick
The proportionality factor Ks of the controlled system is calculated as follows:
(11)
Y
X
s
K
∆
∆
=
english