107
Auxiliary functions
Type 8792, 8793 REV.2
16.1.16.2.
OUT BIN1 / OUT BIN2
- Configuring the binary outputs
The following description is valid for both binary outputs
OUT BIN 1
and
OUT BIN 2
, as the operation in the
menu is identical.
The binary outputs 1 and 2 can be used for one of the following outputs:
POS.Dev
Exceeding the permitted control deviation
POS.Lim-1/2
Current position with respect to a specified limit position (> or <)
Safepos
Actuator in safety position
ERR.SP/CMD
Sensor break (SP = process set-point value / CMD = set-point value position)
ERR.PV
Sensor break (process actual value).
Available for Type 8793 only.
Remote
Operating state (AUTOMATIC / MANUAL)
Tune.Status
Status
X.TUNE
(process optimization)
DIAG.State-1/2
Diagnostic output (option)
Overview of possible outputs and associated switching signals:
Menu option
Switching signal Description
POS.Dev
0
Control deviation is within the set limit.
1
Control deviation is outside the set limit.
POS.Lim-1/2
0
Actual position is above the limit position.
1
Actual position is below the limit position.
Safepos
0
Actuator is not in the safety position.
1
Actuator is in the safety position.
ERR.SP/CMD
0
No sensor break available.
ERR.PV
1
Sensor break available.
Remote
0
Appliance is the AUTOMATIC operating state.
1
Appliance is the MANUAL operating state.
Tune.Status
0
The
X.TUNE
function is currently not running.
1
The
X.TUNE
function is currently running.
0/1 alternating
(10 s)
The
X.TUNE
function was stopped during execution by a fault.
DIAG.State-1/2
0
No diagnostic message available for the selected status signals.
1
Diagnostic message available for the selected status signals.
Table 34:
OUT BIN 1/2; possible outputs and associated switching signals
Switching signal
Switching statuses
normally open
normally closed
0
0 V
24 V
1
24 V
0 V
Table 35:
OUT BIN 1/2; switching statuses
english