136
Auxiliary functions
Type 8792, 8793 REV.2
In addition to the monitor there is a temperature slave pointer. This indicates the lowest and highest of the
measured temperature values. The slave pointer can be reset by pressing the
CLEAR
key.
Display
TEMP.CHECK
Description of the functions
EXIT
29-8-1
TEMP.CHECK
CURRENT
MAX
MIN
LIMIT
21.7 *C
21.7 *C
21.7 *C
CURRENT
indicates the current temperature.
MAX
indicates the highest temperature of the slave pointer
MIN
indicates the lowest temperature of the slave pointer.
The permitted temperature range can be changed in the
LIMIT
submenu. A message is output if the temperature goes outside the per-
mitted range. The temperature range has been preset at the factory from
0...60 °C.
The history entries of the last 3 messages can be viewed and deleted in
the
HISTORY
submenu.
EXIT
ENTER
29-8-1
LIMIT
HISTORY
Table 46:
TEMP.CHECK; temperature range
Specify the temperature limit for outputting messages as follows:
→
/ Select
TEMP.CHECK
.
(To do this, the
TEMP.CHECK
function must be incorporated into the
DIAGNOSE
main menu. See
chapter “16.1.24.3. Activation of diagnostic functions”).
→
Select
ENTER
. The menu is displayed.
→
/ Select
LIMIT
.
→
Select
ENTER
.
The upper and lower temperature limit is displayed.
The upper limit
TEMP.MAX
has already been selected.
→
Select
INPUT
. Open input screen for upper temperature limit.
→
/
+
Increase value
<-
Changing the decimal place
Enter upper temperature limit
TEMP.MAX
.
→
Select
OK
. Acknowledge value.
→
/ Select
TEMP.MIN
.
→
Select
INPUT
. Open factory setting for lower temperature limit.
→
/
+
Increase value
<-
Changing the decimal place
Enter lower temperature limit
TEMP.MIN
.
→
Select
OK
. Acknowledge value.
→
Select
EXIT
. Return to the
TEMP.CHECK
menu.
→
Select
EXIT
. Return to the
DIAGNOSE
main menu.
You have specified the
temperature limit for outputting messages.
english