167
EtherNet/IP, PROFINET and Modbus TCP
Type 8792, 8793 REV.2
NOTE
To ensure electromagnetic compatibility (EMC), use a shielded Ethernet cable. Ground the cable
shield on both sides, on each of the connected devices.
For the grounding use a short line (max. 1 m) with a cross-section of at least 1.5 mm
2
.
FE functional earth
Figure 67:
Functional earth
19.7
Bus status display
The bus status is indicated on the display on the device.
Display
(is displayed approx.
every 3 seconds)
Device state
Explanation
Troubleshooting
BUS no
connection
Online,
no connection to
the master.
Device is connected correctly
to the bus, the network access
procedure has ended without
errors, however there is no
established connection to the
master.
•
New connection established
by master.
BUS
critical err
Critical bus error.
Other device with the same
address in the network.
BUS offline
due to communi-
cation problems.
•
Change address of the
device and restart device.
•
Fault analysis in the network
with a bus monitor.
Table 59:
Bus status display; Ethernet