98
Auxiliary functions
Type 8792, 8793 REV.2
→
/ Enter value: Closing time for total stroke (in seconds)
Adjustment range: 1...60 seconds
+
Increase value
-
Reduce value
→
Select
OK
*. Acknowledge input and return to the display of
X.TIME.
You have entered the limit of the control speed.
* If the submenu is left by pressing the ESC key, the value remains unchanged.
The changed data is saved in the memory (EEPROM) only when there is a switch to the process
level, by leaving the main menu (MAIN) using the left selection key
EXIT
.
Effect of limiting the opening speed when there is a jump in the set-point value
Set-point
value
Actual
value
Open
t
Valve stroke [%]
(
POS
,
CMD
)
Figure 38:
X.TIME graph
16.1.10
X.CONTROL –
Parameterization of the positioner
This function can be used to re-adjust the parameters of the positioner.
The re-adjustment should only be made if it is required for the application.
The parameters for
X.CONTROL
are automatically set with the exception of
DBND
(dead band) when
specifying the basic settings by running
X.TUNE
.
If the setting for DBND (dead band depending on the friction behavior of the actuating drive) is also
to be automatically determined when
X.TUNE
is running,
X.CONTROL
must be activated by incorpo-
rating it into the main menu (MAIN).
When
X.TUNE
is running, all previously re-adjusted values are overwritten (except the
X.TUNE
function was manually parameterized).
DBND
Insensitivity range (dead band)
KXopn
Amplification factor of the proportional portion (for aerating the valve)
KXcls
Amplification factor of the proportional portion (for bleeding the valve)
KDopn
Amplification factor of the differential portion (for aerating the valve)
KDcls
Amplification factor of the differential portion (for bleeding the valve)
YBfric
Friction correction (for aerating the valve)
YEfric
Friction correction (for bleeding the valve)
english