Connect L1 and L2 to the input safety breaker. BTCPower highly recommends crimp ferrule lugs
to be used to make all electrical connection to the input safety breaker. In addition, a torque
wrench should be used on the input breaker screw terminals. Set the wrench to a torque of
80lb.in or 9 N.m. A pull test should be done on the wire connections to ensure proper
connection.
SquareD Breaker (BDL26100)
Charger
Wire Size Range
Torque Requirement
70A
6
–
3 AWG (recommended)
80 lb.in
(9 N.m)
* Temperature rating of wires should be 60°C for 3AWG and 90°C for 6AWG. Use Copper wires only.