AC Level 2 Charger
INSTALLATION AND USER’S MANUAL
Page
32
of
59
This document is a
Property of BTCPower Inc.
and shall not be
copied, reproduced, or used as the basis for sale or manufacture
of apparatus without written permission.
09-Mar-20
Revision
T
Single
Port Charger
(30A/40A)
–
Pedestal
Connect L1 and L2 to the input safety breaker. BTCPower highly recommends crimp ferrule lugs
to be used to make all electrical connection to the input safety breaker. In addition, a torque
wrench should be used on the input breaker screw terminals. Set the wrench to a torque of
21.2 lb.in or 2.4 N.m. A pull test should be done on the wire connections to ensure proper
connection.
Eaton Breaker (FAZ-C50/2)
Charger
Wire Size
Torque Requirement
30A
10
–
8AWG (recommended)
21.2 lb.in
(2.4 N.m)
40A
8
–
6AWG (recommended)
* Temperature rating of wires should be 60°C. Use Copper wires only.
NOTE
Appropriate wire size / gauge to be used will be determined by the installer in-charge.
INSTALLATION