INSTALLER’S GUIDE
Page 17
After checking, turn
off the appliance.
Remove the pressure
gauge and replace
the test point sealing
screw. Relight the
appliance. Turn to
the maximum output
position and test
around the sealing
screw for gas
soundness with a
suitable leak
detection fluid.
If all the above
checks are
satisfactory, continue
with the installation.
If not, check the control and ignition circuitry and components as described in the
servicing section of this manual.
5.3
Test For Spillage
A spillage test must be made before the installed appliance is left with the customer.
5.3.1
Close all doors and windows in the room containing the fire.
5.3.2
Light the appliance and set the control knob to the maximum position (Position 4).
5.3.3
Leave the appliance on for seven minutes.
5.3.4
Insert the smoke match tube (with lighted match) into the side of the appliance and
against the back panel. Position the tube so that it is horizontal, against the back panel
and with its top edge touching the side of the draught diverter box. Slide the tube until
the indent in the tube is level with the diverter side. See figure 13.
5.3.5
The installation is satisfactory if the smoke is drawn into the diverter box. If an
appreciable amount of smoke escapes from above the flue spigot or from the sides leave
the appliance alight at the maximum setting for a further ten minutes and then repeat the
test.
If the test is still unsatisfactory disconnect the appliance and seek expert advice.
5.3.6
If the above test is satisfactory, open all internal connecting doors, hatches, etc. in
the room. Keep all doors and windows that open to the outside of the building closed.
recheck for spillage as above. If an extractor fan is installed in the same room as the
appliance or a connecting room, check that spillage does not occur with the fan operating
and all doors and other openings between the fan and the appliance open. If the test is
satisfactory continue with the installation.
If the test is not satisfactory disconnect the
appliance and advise the customer of the cause of failure.
Figure 13 Smoke match tube position