System settings (Service menu – Settings)
Logamatic EMS – 6 720 801 387 (2011/05)
44
6
6.7
RC35 calibration
B
Turn the
rotary selector to the left until
RC35
calibration
is selected
B
Press button
to select
RC35
calibration.
The menu for
SETTING/RC35 CAL
is opened.
Calibrating the displayed room temperature (calibration)
If there is a separate thermometer near the programming unit, it may show a different room
temperature to that shown on the programming unit. You can use this function to adjust (“calibrate”)
the programming unit to match the thermometer.
Before adjusting the room temperature, consider the following:
• Is the thermometer more accurate than the programming unit?
• Is the thermometer located close to programming unit so that they are both subject to the same
heat influences (e.g. sunlight, fireplace)?
Example: if the thermometer is showing a temperature 0.5 °C higher than the programming unit,
enter
+0.5 K
as the calibration value.
Menu item
Input range
Standard setting
Other
information
RC35 calibration
– 5.0 K to +5.0 K
0.0 K
Table 18 Navigator for service menu SETTINGS\CALIB. RC35
A thermometer may indicate temperature fluctuations more slowly or rapidly than the
programming unit.
B
Therefore, never calibrate the programming unit during phases when the heating
system is cooling down or heating up.