System settings (Service menu – Settings)
6
6.4
Heating circuit data
This chapter explains the settings for all heating circuits using heating circuit 1 as an example.
B
Turn the
rotary selector to the left until
heating circuit 1
is selected.
B
Press
to select
heating circuit 1
.
The menu for
SETTING\HEATING CIRCUIT 1
is opened.
Menu item
Input range
Standard
setting
Other information
Do you want to enable
heating circuit 1?
Yes, No
Yes
Which programming unit
is assigned to heating
circuit 1?
RC2x/RC20/RF,
RC35, none
RC35
See page 35. With UBA1.xyou can
not select RC2x.
With selection of“None”the control
mode is switched to“Outside
temperature” compensatedand it is
hidden.
How should heating
circuit 1 be controlled?
Outside
temperature
compensated,
room temperature
compensated
Outside
temperature
compen-
sated
“Room temperature compensated”
can only be set if RC2x or RC35 has
been allocated. If “room temperature
compensated” is selected, room
flow is used.
Which heating system
does heating circuit 1
have?
Radiator,
convector, floor
Radiator
With HK1 “underfloor” setting only if
it is a case of a oil/gas condensing
boiler. Additional heating circuits
can then be installed.
Use a safety thermostat with
underfloor heating systems.
Table 14 Navigator for service menu of SETTING\HEATING CIRCUIT 1
SERVICE\SETTINGS
B
plant data
boiler data
domestic hot water
heating circuit 1