System settings (Service menu – Settings)
Logamatic EMS – 6 720 801 387 (2011/05)
32
6
Heating curve
Std. tmp. ( – 10 °C)
30 °C to 90 °C
75 °C
(radiator,
convector)
45 °C
(floor)
The value in brackets is the setting
for the minimum outside
temperature (
Æ
page 31). Setting
only if the control mode is set to
“outside temperature
compensated”(
Æ
page 36).
Max flow temp.
Radiators,
convectors: 30 °C
to 90 °C.
1)
Underfloor heating:
30 °C to 60 °C
Radiators,
convectors:
75 °C
Underfloor
heating:
50 °C
Setting only if the control mode is
set to“outside temperature
compensated”(
Æ
page 36).
Enter the maximum
flow temperature:
Setting only if the control mode is
set to“room temperature
compensated”(
Æ
page 36).
Min flow temp.
5 °C to 70 °C
5 °C
Setting only if the control mode is
set to“outside temperature
compensated”(
Æ
page 36)
Enter the minimum flow
temperature:
Setting only if the control mode is
set to“room temperature
compensated”(
Æ
page 36).
Rm. tmp. offset
-5.0 K to +5.0 K
0.0 K
Offset of heating curve.
Setting only if the control mode is
set to “outside temperature
compensated”(
Æ
page 36).
Enter the maximum room
influence:
0 K to 10 K
3 K
Setting only if the control mode is
set to “outside temperature
compensated”(
Æ
page 35).
Which reduction mode
should be implemented?
Outdoor
compensation
mode,
reduced mode,
room compensation
mode (only if RC35
or RC2x have been
allocated to the
heating circuit),
switch-off mode
Outdoor
setback
mode
Night reduction
(
Æ
page 37)
Menu item
Input range
Standard
setting
Other information
Table 14 Navigator for service menu of SETTING\HEATING CIRCUIT 1