background image

Analog fire panels

FPA-1000 Family

en

Installation and Operation Guide

Содержание FPA-1000-UL

Страница 1: ...Analog fire panels FPA 1000 Family en Installation and Operation Guide ...

Страница 2: ......

Страница 3: ...onsiderations 23 3 2 1 Ground Fault Detection 23 3 3 Configuration and Programming Basics 24 3 3 1 Points 24 3 3 2 Advanced Point Features and Processing 26 3 3 3 Events 29 3 3 4 Zones 31 3 3 5 Special Alarm Features 34 3 3 6 Sequential Reset 36 3 3 7 Multi combined multi separated Alarm Modes 36 3 3 8 External Signaling 36 3 4 Address Assignment 36 3 4 1 Option Bus Address Assignment 37 3 4 2 SLC...

Страница 4: ...s 79 5 3 Keypads 80 5 4 Keypad Operations 84 5 5 System Normal Displays 86 5 6 Off normal Displays 88 5 7 Menu Navigation and Structure 90 5 7 1 Menu Structure 92 5 8 Browser Navigation and Structure 98 5 8 1 Off site and on site access 98 5 8 2 Working with web pages 99 5 9 Overview of the web user Interface 100 6 Diagnostics and Troubleshooting 103 6 1 Phone monitor troubleshooting 103 6 2 Diagn...

Страница 5: ... of contents en 5 Bosch Security Systems Inc Installation and Operation Guide 2017 11 2 0 F 01U 173 607 9 4 Reporting Codes 128 9 5 FPA 1000 UL Operating Instructions Sheet 135 9 6 FPA 1000 V2 Operating Instructions Sheet 137 ...

Страница 6: ...The Installation and Operation Guide does not contain special information about local requirements and safety issues Information on such issues is provided only to the extent that it is needed for operation of the device Ensure that you are familiar with all safety related processes and regulations in your area This also includes How to act in the event of an alarm Initial steps to take if a fire ...

Страница 7: ... into an outlet on a circuit different from that to which the receiver is connected Consult the dealer or an experienced radio or TV technician for help FCC Phone Connection to Users This control panel complies with Part 68 of the FCC rules On the inside of the enclosure is a label that contains among other information the ringer equivalence number REN for this equipment You must upon request prov...

Страница 8: ...rruption in telephone service 1 4 NFPA Standard 72 NFPA 72 the National Fire Alarm and Signaling Code for the United States is one of the standards referenced in this manual The current edition 2016 of this standard is available at a nominal cost from The National Fire Protection Association Batterymarch Park Quincy MA 02269 Older editions of the standard identified circuit types by Class and Styl...

Страница 9: ...E 1000 SLC doubling the address points The panel has a compact and solid metal housing with a removable front door with keyed lock and a removable dead front door to access electronics It features surface and semi flush mounting options On the front of the panel six light emitting diodes LEDs show fire alarm gas alarm power supervisory silence and trouble conditions The built in keypad can be used...

Страница 10: ...fire panels 2017 11 2 0 F 01U 173 607 Installation and Operation Guide Bosch Security Systems Inc Figure 2 1 FPA 1000 V2 System architecture Optional Networking Cards allow multiple panels to be interconnected into a networked system ...

Страница 11: ... Twisted pair wire CAT 5 cable or fiber optic cable used on network connections Programmable sensitivity levels per device and automatic day and night sensitivity modes Automatic calibration and drift compensation routine 120 V 240 V AC power total 5 5 A transformer output Two integrated NAC circuits rated at 2 5 A each allowing up to 4 A total current shared between AUX power Option Bus and NAC U...

Страница 12: ...tion for sandwich alarm allows time triggered phased evacuation evacuation floor by floor Auto Learn feature for easy start up programming Local piezo sounder Fire drill test function Walk test function Alarm verification feature Bypass or unbypass point output or zone individually 2999 events history buffer Event and history printing via network printer Three language versions English Spanish and...

Страница 13: ...th FPE 1000 SLC Plug in Module Nominal 39 V DC 30 to 40 V DC 260 mA maximum per SLC power limited supervised Option bus Provides serial data interface with 500 mA at 12 V DC power limited supervised AUX FWR FWR RST RST Two auxiliary power supply terminals with 500 mA at 24 V DC each power limited non supervised FWR Full Wave Rectified non switched RST Resettable switched and filtered NAC 1 NAC 2 T...

Страница 14: ...osch Security Systems Inc to be used with the FPA 1000 fire panels For a complete description of and installation instructions for each product refer to the appropriate section of this manual and the documents supplied with the device 2 4 Plug in Modules The following plug in modules are available for the FPA 1000 fire panels Type Number Description FPE 1000 NE Ethernet Networking Card FPE 1000 NF...

Страница 15: ...de higher capacity Each FPA 1000 provides two auxiliary power supplies one 0 5 A at 24 V FWR one 0 5 A at 24 V DC RST resettable This auxiliary power can run expansion boards or other low current auxiliary devices For a list of Bosch batteries and battery boxes see the following table For selecting the necessary battery capacity use the Microsoft Excel based FPA 1000_Battery_Calculator xls The spr...

Страница 16: ...isory functions and with power and trouble LEDs plus eight zone LEDs that can be individually labeled D7030X S8 Annunciator 8 LED 8 supervisory with eight zones reserved for supervisory functions and with power and trouble LEDs plus eight zone LEDs that can be individually labeled D7032 Annunciator expander 8 LED attaches to a D7030X D7030X S2 or D7030X S8 and identifies the location of a fire ala...

Страница 17: ... monoxide CO sensor as an indicator of fire Provides two user selectable modes for making the fire decision multi combined and multi separated mode Allows programming LED behavior during polling of the internal device LED and a remote connected indicator D models incorporate dual photoelectric emitters infrared and blue to enhance catch performance Can use addresses 1 to 254 FAP 325 V2F SMOKE P An...

Страница 18: ...the advanced analog communication protocol except the FAD 325 DH or FAD 325 V2F DH 6 in 15 cm diameter ISO base contains built in circuit isolator FAD 325 FAD 325 DH FAD 325 R FAD 325 V2F FAD 325 V2F DH FAD 325 V2F R SMOKE D Analog Duct Smoke Sensor Replacement Analog Duct Smoke Detector Provides early detection of smoke and products of combustion present in air moving through HVAC ducts in Commer...

Страница 19: ...tor 4 inch Class A The types FLM 325 IM FLM 325 I4 AI and FLM 325 I4 A can use addresses 1 to 254 FLM 325 2I4 CONT MOD Dual Input Monitor Provides two independent contact monitoring circuits while utilizing only one address on the SLC Can be programmed to monitor normally open or normally closed contact fire alarm and supervisory devices NO EOL NC EOL NC no EOL Supervises with Style B Class B loop...

Страница 20: ...D328A RELAY MOD Analog Relay Module Allows the control of one Form C contact rated for 1 0 A at 30 V DC or 0 5 A at 125 V DC for a variety of normally open NO and normally closed NC contact applications such as elevator recall systems or HVAC shutdown Loop powered FLM 325 N4 NAC MOD Supervised Output Module Provides a supervised pole reversal output used for acoustic and optical signaling devices ...

Страница 21: ... are programmable Two different phone numbers or IP addresses or one phone number and one IP address Different dialing types for PSTN pulse only tone and pulse or tone only Individual PSTN line supervision audible and visible trouble signal in the case of a transmission path failure Selectable options for Report Steering Groups Programmable supervision time for each Conettix IP reporting account T...

Страница 22: ...plete understanding of specific features of the fire control panel and related peripherals see the following documentation NAC Compatibility List Operating Instruction Sheet FPA 1000 Wiring Diagram Release Notes Installation Guide FPE 1000 SLC Signaling Line Circuit Installation Guide FPE 1000 CITY City Tie Plug in Module Installation Guide FPM 1000 SFMK Semi flush Mounting Kit Installation and Op...

Страница 23: ... Codes and the Authority Having Jurisdiction AHJ 3 1 Power Supply Calculations To select the proper battery size for your system calculate the required total current draw of your system using the Microsoft Excel based FPA 1000_Battery_Calculator xls The spreadsheet can be downloaded at www boschsecurity us 3 2 Network Wiring Connection Considerations Notice The FPA 1000 s network created by using ...

Страница 24: ...or is activated The point is dirty if the clean air value reaches a defined upper limit depending on detector type This takes place automatically during the calibration processes After the panel is initialized successfully the test interval for the calibrated detector sensitivity testing is4 hours The dirty condition is handled as a trouble status If the clean air value is out of range a calibrati...

Страница 25: ...efault point type P possible point type Blank not available SMOKE x includes SMOKE M FAP 440 T FAP 440 TC FAP 440 DT FAP 440 DTC SMOKE P FAP 325 FAP 325 V2F FAP 440 FAP 440 D SMOKE I FAI 325 and SMOKE D FAD 325 FAD 325 R FAD 325 DH FAD 325 V2F FAD 325 V2F R FAD 325 V2F DH HEAT FAH 325 FAH 440 CONVZ MOD FLM 325 CZM4 CONT MOD FLM 325 2I4 FLM 325 I4 FLM 325 I4 A FLM 325 I4 AI FLM 325 IM FMM 325A and ...

Страница 26: ...d point feature P Programmable point feature G Dependent on global setting Blank not available Tab 3 14 Mapping point types to point features The following principles apply For Supervisory point type programming of latching or non latching is panel wide The point types Generic Trouble AC failure Battery Failure Reset Silence Drill and Acknowledge are non latching see Points page 24 For the Fire Au...

Страница 27: ...senses detector in alarm and retards delays alarm signal Fixed 20 seconds B C POWER UP PERIOD Power to the detector is reapplied and time is allowed for detector to become operational for alarm detector restart Time depends on the device type detector maximum 3 seconds Conventional Zone Module maximum 10 seconds A C RETARD RESET RESTART PERIOD No alarm obtained from control unit Not configurable 3...

Страница 28: ...to point type Waterflow with delay The Waterflow delay enable option is arranged on a per point basis Each point configured with Waterflow delay has its own timer The Waterflow delay timer is user programmable ranging from 10 to 90 seconds The default is 90 seconds The input point must remain constantly in an active state for the complete time delay Any interruption resets the timer Latching If a ...

Страница 29: ...hin 15 seconds of annunciation at the system s operator interface The system is not manually reset within the programmed PAS investigation time of the acknowledgment described in a When a second automatic fire detector selected for positive alarm sequence actuates before the system is reset as described in b or when any other fire initiating device reporting to the system or control unit actuates ...

Страница 30: ...to which the event belongs see the following table Point Type Event or Operation Event Group by Point Activation by Point Deactivation by Activation by Deactivation Fire Auto Fire alarm Fire alarm restore Alarm Fire Alarm Manual Fire alarm Fire alarm restore Alarm Waterflow Waterflow alarm Waterflow alarm restore Alarm Supervisory Non latching Fire supervisory Fire supervisory restore Supervisory ...

Страница 31: ...ator recall Input points Smoke detectors pull stations and so on Zone A group of input points zones 1 to 225 are configurable 226 to 234 are activated automatically Outputs Notification Appliance Circuits NACs such as bells strobes and relays Zone mapping on a networked system For each panel on the network there are 128 local zones pp 001 to pp 128 where pp the panel ID Local zones are used to ass...

Страница 32: ...lobal zones and are hard coded to pre assigned conditions They are automatically activated by inputs if a special condition occurs or the panel is in a processing sequence See the following two figures It is not possible to assign an input point to any global zone An output can be assigned to a global zone so that it will be activated upon the corresponding special condition For example any input ...

Страница 33: ...al waterflow Tab 3 18 Pre assigned zones In some cases if a relay output is assigned to a certain global zone other assigned zones are ignored Mainboard relay 1 If assigned to the global alarm zone other assigned zones are ignored The relay reacts only to the global alarm zone Mainboard relay 2 If assigned to the global trouble zone other assigned zones are ignored The relay reacts only to the glo...

Страница 34: ...red active only when two or more input points assigned to that zone are active It is not allowed to assign an input point programmed with any delayed point features including PAS Pre signal alarm verification and PAS day or alarmverification night to a counting zone Notice When implementing the counting zone feature a minimum of two detectors is required in each protective space Also all points on...

Страница 35: ...ny dual zone dependency Sandwich Alarm The sandwich alarm feature allows for the time triggered phased evacuation floor by floor in case of a fire alarm inside a building All NAC zones can be grouped by floor This is achieved by assigning NACs to local or group zones then assigning zones to floors These floors are logically mapped to floors in a building where adjacent floors are mapped to neighbo...

Страница 36: ...vity is modified by input from the CO sensor These detectors have two alarm modes for making the fire decision multi combined mode or multi separated mode In the multi combined mode the alarm is activated by either the smoke or heat sensor or by both The detector essentially works as a photoelectric smoke detector modified according to the temperature and the CO level if a carbon monoxide sensor i...

Страница 37: ...upports up to eight pairs of D7030X Family D7032 annunciators allowing a total of 128 8 x 16 zone LED indications All D7030X D7032 LEDs are mapped to either not both local 1 128 or group 129 225 zones For an explanation of how to map the LEDs to zones see the following table Option Bus Address Local Zones Group Zones D7030X D7032 D7030X D7032 1 1 8 9 16 129 136 137 144 2 17 24 25 32 145 152 153 16...

Страница 38: ...54 detectors and modules or up to 127 analog sounder bases in combination with a suitable detector for a total of 254 addressable device capacity per SLC For a list of permitted address ranges for SLCs see the following table Device Category Device Group Type Type Number Address Range Detector SMOKE M FAP 440 T 1 254 FAP 440 TC 1 254 FAP 440 DT 1 254 FAP 440 DTC 1 254 SMOKE P FAP 325 1 127 FAP 325...

Страница 39: ... SLC module is limited to 32 Each device on the SLC must have a unique address A double address trouble is reported but can be resolved only automatically by the panel For instructions on programming the address into each analog addressable device see Addressing SLC devices in SLC module page 61 3 4 3 Mainboard Address Assignment The mainboard addresses are used for the event reporting see Reporti...

Страница 40: ...nized with events on another panel or panels Tab 3 24 Mainboard address assignment 3 5 Reporting Requirements Notice For UL Listed Fire Installations shared on premises communications equipment must be UL Listed for Information Technology Equipment The communicator can report to two phone numbers two IP addresses or one phone line and one IP address with full single double and back up reporting Ca...

Страница 41: ...tion receives the automatic test report only every other time this indicates that one phone line at the protected premises is inoperative Correct this condition immediately because other critical reports can be delayed when the communicator is trying to send the test signal through the inoperative phone line Because the control panel automatically selects which line to use both phone lines must us...

Страница 42: ... X 13 X X 14 X X 15 X X 16 X X 17 X X 18 X X 19 X X 20 X X Tab 3 25 Phone line attempt matrix Supervision time in seconds ACK wait s x retries Polling rate s Configured Supervision Time Acknowledge wait time Heartbeat interval1 Communication tries 90 sec 5 sec 30 sec 5 180 sec 15 sec 60 sec 5 200 sec 15 sec 80 sec 5 5 min 15 sec 180 sec 5 1 The heartbeat interval includes a built in minimum 30 sec...

Страница 43: ...indicated below For a list of the required program entries and required accessories for UL Listed Commercial Fire Alarm installations Central Station DACT and Local see the following table Program Feature or Option Permitted in UL 864 Possible Settings Settings Permitted in UL 864 Remote Programming Yes REMOTE PROG 1 CONFIRM AT PANEL 2 ENABLE 3 DISABLE 1 CONFIRM AT PANEL 3 DISABLE Mainboard Relay ...

Страница 44: ... UL Listed smoke detector with a base At least one horn strobe or bell listed in the NAC Compatibility List providing 85 dB for UL864 and NFPA 72 requirements is required for this application and must be installed inside the protected area Four wire detectors must be used with UL Listed power supervision devices All devices must be used with the End of Line EOL resistor provided Configuration Requ...

Страница 45: ...Communications Programming if Used for Central Station Service Select a communication format that is compatible with the central station then enable both phone lines 3 7 NFPA Standard specific Requirements The FPA 1000 Analog Addressable Fire Panels are designed for use in commercial industrial and institutional applications and meet the requirements for service under the National Fire Protection ...

Страница 46: ...evacuation signals 3 8 Fire Safety Considerations No fire detection device or system is 100 incapable of failure This fire alarm system can provide early warning of a developing fire Such a system however does not ensure protection against property damage or loss of life resulting from a fire Any fire alarm system can fail to warn for any number of reasons such as smoke not reaching a detector tha...

Страница 47: ...s to keep their bedroom doors closed and to exit the building by alternate routes If the top of the door is not uncomfortably hot then brace the bottom of the door with your foot and the top with one hand then open the door about one inch Be prepared to slam the door shut if there is any pressure against the door or if any hot air rushes in If there is no evidence of excessive heat or pressure the...

Страница 48: ...vices function as NACs for example sounder bases or strobes The SLC devices that are on the same SLC are synchronized with each other but they are not synchronized devices on the other SLC nor with the mainboard or RNAC NACs 4 2 Installation Considerations for UL Listed Systems Install the control panel according to NFPA 72 for Commercial Fire installations Failure to install and program this equi...

Страница 49: ...glish X X X Electronic Document Downloads Sheet multi language X X X Tab 4 29 Components included with FPA 1000 panels Notice Attach the wiring label onto the inside of the front door The Operating Instruction Sheet must be framed and mounted in view adjacent to the fire panel A second Signaling Line Circuit SLC the City Tie Plug in Module FPE 1000 CITY and a Networking Card FPE 1000 NE FPE 1000 N...

Страница 50: ...ries 24 V FWR 17 to 31 V FWR 500 mA Refer to the manufacturer s installation instructions of the connected device for proper wiring and other limitations AUX power is non supervised For proper supervision use an end of line EOL power supervision device such as a D275 AUX RST RST Resettable switched and filtered Connects to 4 wire smoke detectors 24 V DC 17 to 31 V DC 500 mA Refer to the manufactur...

Страница 51: ...aximum line resistance 65 Ω RELAY 1 2 3 NO C NC Connects to external devices activated or inactivated in defined condition 30 V DC 5 A 120 V AC 10 A LINE 1 LINE 2 Connects to PSTN 2 lines RJ45 Telephone cord such as the D162 Dual modular phone cord ETHERNET Connects to Ethernet RJ45 To connect a computer directly to the panel use cross over or straight CAT 5 cable The FPA 1000 V2 panel supports au...

Страница 52: ... cabinet door and dead front door fully and to easily install wire and maintain the panel The cabinet can be either semi flush or surface mounted Depending on the configuration and the battery selection the FPA 1000 can weigh more than 55 lbs 25 kg When attaching the enclosure to a surface use mounting hardware not supplied capable of supporting this weight and reinforce the wall as necessary Obse...

Страница 53: ...ockout 1 Hole mounting 2 Holes securing Surface mounting The enclosure mounts using one hole mounting located at the top of the back box refer to Item 1 in the figure above and two securing holes located in the lower section refer to Item 2 in the figure above 1 Using the enclosure as a template mark the top mounting hole on the mounting surface refer to Item 1 in the figure above 2 Start the moun...

Страница 54: ...nting hardware For semi flush mounting between studs use the three holes on each side of the enclosure for the screws refer to Item 1 in the figure below Use four screws to fasten the trim ring refer to Item 2 in the figure below Notice In a semi flush mounting of the enclosure if the screws are over tightened or the enclosure is set too deep the trim ring might not fit properly The sides of the e...

Страница 55: ...nward with finger pressure refer to Item A in the figure below and open with a quarter turn of the fastener head refer to Item B in the figure below A B Figure 4 4 Dead Front Door 4 6 Installing the Mainboard Caution Static sensitive components ground yourself before handling The mainboard and some modules contain static sensitive components Use a wrist strap connected to ground or touch ground to...

Страница 56: ...d Power Trouble Fire DRILL RESET SILENCE ACK Supervisory _ A a Gas Alarm Silenced Power Trouble Fire DRILL RESET SILENCE ACK Supervisory _ A a DRILL RESET SILENCE ACK 2 1 3 Gas Alarm Power Fire DRILL RESET SILENCE ACK Gas Alarm Silenced Power Trouble Supervisory Fire Figure 4 5 Inserting the language tab Mounting the Mainboard 1 Take the mainboard support out of the accessory bag and place it onto...

Страница 57: ...talling Optional Plug in Modules The mainboard allows for the installation of plug in modules The plug in modules connect directly to the mainboard They are enabled by programming and supervised by the control panel See Mounting plug in modules page 58 The first FPE 1000 SLC Signaling Line Circuit is mandatory equipment at the top position on the mainboard A second FPE 1000 SLC plug in module can ...

Страница 58: ...nted in essentially the same manner The procedure for mounting an SLC card is given as an example Note that the City Tie Module and Networking Cards do not have ground wires 1 Bring the plug in module into position with the horizontal terminal lettering facing the front side of the control panel Slide the plug in module carefully into position see callout 1 in the following figure 2 Ensure that th...

Страница 59: ...S1 Switch 1 Fire Alarm S2 Switch 2 Supervisory 1 DIP switch setting for Reverse Polarity mode 2 DIP switch setting for Local Energy mode FPE 1000 CITY S1 Fire Alarm S2 Supervisory DIP switches 1 2 3 1 2 3 Reverse Polarity mode ON ON ON ON ON ON Local Energy mode OFF OFF OFF OFF OFF OFF Notice You can use different operation modes for the circuits The DIP switch settings 1 to 3 for each switch S1 a...

Страница 60: ...see the following figure Figure 4 10 City Tie wiring in reverse polarity mode M Monitoring station In normal conditions the FPE 1000 CITY sends a steady current to a monitoring station In an alarm condition it reverses the polarity of the output current The module signals a trouble condition by interrupting the output voltage and current The default setting is fire alarm for circuit 1 and supervis...

Страница 61: ...l energy mode Notice The shunt connection is recognized only as a supplementary signaling unit as part of a local control unit and is not recognized as an auxiliary control unit connection per NFPA 72 For listing of compatible Gamewell devices see Plug in Modules page 14 4 7 3 SLC module The Signaling Line Circuit is power limited and supervised Signaling line circuits can be wired as Class X Clas...

Страница 62: ...imum permissible values apply Wiring resistance on the SLC must be less than 50 Ω Circuit capacitance must be less than 1 μF Circuit inductance must be less than 1 mH The total wire length of all branches connected to one FPE 1000 SLC module terminals S1 SC1 and S2 SC2 must not exceed 30 000 feet 9140 m for Class B See the following figure Figure 4 12 Total length for SLC Class B wiring The maximu...

Страница 63: ...device and control its functionality All listed addressable devices come from the factory preset to address 127 This preset address can only be reprogrammed using the D5070 Analog Device Programmer Devices must not be powered when using the D5070 Analog Device Programmer to set addresses The FLM 325 IM Contact Module should not be connected to the SLC when using the D5070 Analog Device Programmer ...

Страница 64: ...tor heads 3 Addressable module 4 in back box type with module adapter plug non polarized 4 Addressable module single gang back box type with module adapter A Power on display current address increase address by 10 B Store displayed address into detector C Power off increase address by 1 D Display of device s address or the detector s analog value RD Red BK Black 4 7 4 Network Connections Network c...

Страница 65: ...isted pair wire shielded or unshielded 2952 ft 900 m maximum actual length depends on wire quality CAT 5 cable shielded or unshielded 3280 ft 1000 m maximum Network circuit styles Network connections can be made as Class X or Class B circuits The network circuit is supervised Class X configuration is recommended because this allows the panels in a network to communicate with each other ensuring ci...

Страница 66: ... not share the same conduit or cable as the outgoing side of the loop 4 Refer to NFPA 72 for additional requirements of Class X circuits Network ground fault detection Warning Ground fault The network cards have built in ground fault detection The ground fault detection is located at Port 1 on all three cards It is also on Port 3 on the FPE 1000 NW card For proper detection ground fault detection ...

Страница 67: ...ACP For additional information see Figure 4 16 Option bus wiring 1 Option bus terminals 2 DATA yellow and green wires 3 POWER black wire Common red wire 12 V Protocol Bosch option bus protocol Voltage 12 VDC nominal power limited supervised Current 500 mA maximum Configuration One Class B Circuit wiring distance 4000 ft 1219 m maximum depending on cable gauge and connected devices Tab 4 35 Option ...

Страница 68: ...Class B A Class A wiring B Class B wiring1 1 For Class B termination use Bosch EOL 2 2 kΩ F 01U 034 504 4 10 2 NAC specifications Mainboard 2 circuits NAC 1 and NAC 2 NAC power from panel Nominal 24 VFWR 17 to 31 VRMS regulated power limited supervised Line impedance 1 45 Ω maximum Maximum load Non synchronized NAC 1 2 5 A and NAC 2 2 5 A Synchronized NAC 1 NAC 2 in total 2 75 A Maximum current li...

Страница 69: ...Relay 3 to indicate global system supervisory zone 131 By programming them to up to five of the zone numbers described for point and zone mapping the zones can be programmed to activate the relays on a variety of conditions In addition programming as gas alarm is selectable Figure 4 18 Mainboard relays All relay outputs in the system have an Energized on normal option This option provides fail saf...

Страница 70: ... is temporarily interrupted while the FPA 1000 transmits data see the following figure After installation verify that the FPA 1000 seizes the phone line Figure 4 20 D162 phoneline wiring 1 D162 or equivalent telephone cord connection to the FPA 1000 panel 2 3 Telco lines 2 ring 3 tip T1 House telephone tip R1 House telephone ring Do not connect registered equipment to party lines or coin operated ...

Страница 71: ...rface card NIC connection 4 14 Power Supply Wiring The FPA 1000 allows for charging up to 40 Ah of batteries with the provided transformer working with 120 V AC or 240 V AC For installations requiring battery capacity higher than 40 Ah a regulated and UL 1481 Listed external power supply can be used The external power supplies connect through the panel s battery terminals and are supervised for AC...

Страница 72: ...y side of the transformer see the following figure Black and white wires to unswitched 120 V 60 Hz or Yellow and white wires to unswitched 240 V 50 Hz circuit 2 Use wire nuts for connections Place a wire nut over the unused black or yellow wire Figure 4 22 Connecting AC power 1 Transformer 2 Wire nut 3 Yellow wire 240 VAC line voltage 4 White wire 120 240 VAC neutral voltage 5 Black wire 120 VAC l...

Страница 73: ...ntion This product requires two 12 V batteries in series for a combined voltage of 24 V The rechargeable battery circuit is supervised for the presence of battery power To select the proper battery size for your system use the Microsoft Excel based spreadsheet FPA 1000 Battery Calculator xls The spreadsheet is can be downloaded at www boschsecurity us Select batteries that meet or exceed the total...

Страница 74: ...otice Use only batteries from same manufacturer and with the same capacity Do not mix batteries For recommended battery manufacturers see the following table Manufacturer Batteries POWER SONIC PS 1270 PS 12170 PS 12180 YUASA NP7 12 NPG18 12 Notice Do not connect the interconnect cable until the system is completely installed Observe the wiring polarity and connect the battery cables to the BATT te...

Страница 75: ...nting the Battery box see the BATB 40 BATB 80 Installation Instructions Connect the wires running from the batteries to the FPA 1000 battery terminals see the following figure Figure 4 25 Connecting backup batteries from a remote enclosure Power supply secondary with battery backup Battery capacity in cabinet in remote battery box 7 0 Ah minimum 40 Ah maximum 7 Ah or 18 Ah 24 Ah or 38 Ah Battery c...

Страница 76: ...t auxiliary devices Any devices powered from the auxiliary power terminals should be considered when determining standby battery size The devices connected must have a wider operating voltage range than 17 V to 31 V Observe that one output is DC and the other is FWR The AUX power outputs are power limited Notice Auxiliary power is not supervised Therefore be sure to use a supervision module when c...

Страница 77: ...ansformer from the AC terminals see item 1 in the figure above 2 Connect S SC terminals of the Dual Input Monitor FLM 325 2I4 to the SLC Connect either side to the next device on the SLC or One side to the FPE 1000 SLC Plug In Module of the FPA 1000 and the other side to the next device on the SLC see item 2 in the figure above 3 Install one UL Listed EOL device Hochiki P N 0400 01000 22 kΩ each b...

Страница 78: ...2222 Maintenance level Level 3 PIN 3333 Programming level Web operator level PIN 0000 Login from web browser for viewing only 1 For special applications PIN assignment for reset silence and drill is required control Tab 5 38 Overview of authority levels and default PINs Caution To prevent unauthorized access to the panel and its various authority levels please change the login credentials for the ...

Страница 79: ... the networked system can be programmed into a networked group Within such a networked system certain programmable device settings can be defined as Panel wide parameters only apply to the specific panel to which the device is connected i e local zones 1 128 Network wide parameters apply to all panels in the network system i e Group zones 129 225 and Global zones 226 234 All monitoring activities ...

Страница 80: ...ing the panel and a second user tries to access the panel First User Second User Access Priority and System Response Local Remote Second and any further user is provided a message Try again later The local login cannot be terminated by a remote login Remote Local Local user can choose if he or she would like to terminate the first user or not If the remote programming option is set to 1 CONFIRM AT...

Страница 81: ...ay turn this POT clockwise to lower display contrast or counter clockwise to increase display contrast Keys The keypad has 22 keys including a 12 key alphanumeric pad similar to a telephone keypad with numbers 0 to 9 asterisk and pound sign Escape ESC enter and arrow keys left right up down The alphanumeric keys are used to enter text information similar to the way telephone keys are used to proce...

Страница 82: ... in Date Time mode Key codes 0 to 9 and are skipped automatically Delete key Invalid After a pause key not pressed for 2 seconds the cursor moves to the next position The character at the actual position is overwritten Special functions for the arrow keys Up Delete Down reserved Left Move input position to the left Right Move input position to the right _ A a Gas Alarm Silenced Power Trouble Fire ...

Страница 83: ...sory condition is registered Silenced Yellow On When an alarm or trouble condition is silenced manually by the user If the system auto silence timer expires Off When no condition is silenced When a silenced condition is corrected Trouble Yellow On When the panel is initializing When the panel registers a trouble condition from a point or the panel When inputs or outputs or other elements are bypas...

Страница 84: ...normal conditions are shown in groups classified as fire alarm gas alarm supervisory and trouble Use the arrow keys to view events or conditions in the same group Up and down keys move the user to the previous or next event The left and right keys switch to other groups Acknowledge During an alarm pressing the Acknowledge ACK key turns off the piezo that is sounding on a keypad or annunciator All ...

Страница 85: ... of the panel when a waterflow type alarm activates If the Waterflow Silencable option is activated the silencing operation on the panel is allowed regardless if there is any waterflow alarm Otherwise the silence operation is not performed Respectively any silencing operations including the use of the silence key and automatic silencing are ignored Automatic Silencing The panel provides an automat...

Страница 86: ...reset key is pressed or is automatically cancelled if the operation was started for a programmed time When the drill operation stops the following actions occur All activated NACs turn off A Drill Stop Report is logged into the history and if programmed transmitted to the central station A system reset is automatically performed by stopping the drill so that the panel and all field devices restore...

Страница 87: ...d batteries Scans the keypad for system reset or Enter commands Performs automatic tests on detectors Tests the system memory Display Placeholders For placeholders used for normal off normal and menu display see the following table D Appears in the right upper corner if the system is in Day Mode pp Panel number c or l Circuit number aaa Address s Subaddress MM DD YY Month day year hh mma Hour minu...

Страница 88: ...l conditions is shown The panel stores up to 255 events for each group at a time Any restored event is deleted from the list If more than 255 events exist the newest events are discarded Left and right keys are used to switch between fire alarm gas alarm supervisory and trouble messages The scroll down key is used to view individual messages The ESC key returns the user to the upper level Fire Ala...

Страница 89: ... to normal screen If the point is still in alarm it will display investigating again Gas Alarm Screen Gas Alarms Press v To View Press To View Fire Alarms Supervsr 3 The example above shows three gas alarm messages Press or to view individual gas alarm screens GAS ALM pp l aaa s MM DD YY hh mmayyy xxx Device Type Point Label Supervisory Screen Supervisories Press v To View Press To View Gas Alarms...

Страница 90: ...ntrols unverified activation event from input points programmed as Alarm Verification type and communicator test either automatically by the panel or manually by the user are listed in Controls category Screen for Remote Programming Dialer Trouble TROUBLE pp l aaa s MM DD YY hh mmayyy xxx Dialer Answering 100 The bottom line shows the phone number if no longer than 20 digits or number signs if lon...

Страница 91: ...s The key is not valid on the first three items the key is not valid on the last three items For configuration items the currently selected choice is indicated with an equal sign while others have a space between the shortcut number and the description On a menu with on off actions for example output testing menus the panel indicates the last action performed using an equal sign instead of an arro...

Страница 92: ...INT HISTORY 1 ALL 2 FIRE ALARMS 3 GAS ALARMS 4 SUPERVISORIES 5 TROUBLES 6 CONTROLS 7 COMM RETRIES 3 WALK TEST LOG 4 PRT WALK TEST LOG 2 WALK TEST 1 INPUTS TO TEST single panel no network 1 PANEL WIDE 2 SLC 1 3 SLC 2 4 SELECT ZONES 1 INPUTS TO TEST network enabled 1 NETWORK WIDE 2 SELECT PANEL 3 SELECT ZONES 2 AUDIBLE 1 SILENT 2 SHORT ACTIVATION 3 LONG ACTIVATION 3 START WALK TEST 4 PRT WALK TEST L...

Страница 93: ...SLC 2 DIAGNOSTICS 3 PRINT SLC 1 DIAG 4 PRINT SLC 2 DIAG 3 POWER AND BATT 1 VOLTAGE LEVELS 2 TEST BATTERY NACS 4 OUTPUTS 1 MB OB RELAYS 1 MB RELAY 1 2 MB RELAY 2 3 MB RELAY 3 4 RELAY MODULE 1 9 5 RELAY MODULE 2 10 2 MB OB NACS 1 MB NAC 1 2 MB NAC 2 3 REMOTE NAC 1 11 4 REMOTE NAC 2 12 5 REMOTE NAC 3 13 6 REMOTE NAC 4 14 3 SLC 1 RELAYS 4 SLC 1 LEDS RLEDS 5 SLC 1 NACS 6 SLC 2 RELAYS 7 SLC 2 LEDS RLEDS...

Страница 94: ... 1 THE WHOLE SLC 2 ALL INPUT POINTS 3 SELECT ADDRESS 2 SLC 2 1 THE WHOLE SLC 2 ALL INPUT POINTS 3 SELECT ADDRESS 3 ZONES 1 BYPASS ZONES 1 BYPASS 2 UNBYPASS 4 MB OB OUTPUTS 1 RELAYS 1 MB RELAY 1 2 MB RELAY 2 3 MB RELAY 3 4 RELAY MODULE 1 9 5 RELAY MODULE 2 10 2 NACS 1 MAINBOARD NAC 1 2 MAINBOARD NAC 2 3 REMOTE NAC 1 11 4 REMOTE NAC 2 12 5 REMOTE NAC 3 13 6 REMOTE NAC 4 14 3 CITY TIES 1 CITY TIE 1 2...

Страница 95: ... REMOTE MODULE 1 9 3 REMOTE MODULE 2 10 2 NACS 1 MAINBOARD NACS 2 RNAC MODULE 1 11 3 RNAC MODULE 2 12 4 RNAC MODULE 3 13 5 RNAC MODULE 4 14 3 SILINCE CONFIG 1 AUDIBLE ONLY 2 AUDIBLE VISIBLE 4 ZONE LED RANGE 1 ZONES 1 128 2 ZONES 129 255 5 CITY TIES 1 CITY TIE 1 2 CITY TIE 2 3 BOARD INSTALLED 4 EVENT RANGE 3 ZONES FLOORS 1 DUAL ZONES 1 PAIRS 1 3 2 PAIRS 4 6 3 PAIRS 7 9 4 PAIRS 10 12 5 PAIRS 13 15 6...

Страница 96: ... 6 BYPASS UNBYPASS 3 REMOTE PROG 1 CONFIRM AT PANEL 2 ENABLE 3 DISABLE 4 SILENCE ENABLE 1 ENABLE 2 DISABLE 5 DRILL ENABLE 1 ENABLE 2 DISABLE 6 TIMERS AND SYSTEM 1 TIMERS 1 AC FAIL DELAY 2 AUTO SILENCE 3 WATERFLOW DELAY 4 VERIFICATION 5 SILENCE INHIBIT 6 INVESTIGATION 7 SANDWICH DELAY 8 DUAL ZONE 1ST ALM 9 SEQUENTIAL RESET 2 SYSTEM 1 WATERFLOW SILENCE 2 AUTO SILENCE 3 SUPERVSR LATCH 4 EXTERNAL POWE...

Страница 97: ...RY ACC 3 REPORT STEERING 1 ALARMS 2 SUPERVISORIES 3 ALARM RESTORALS 4 SUPERVISORY RST 5 TROUBLE RESTORE 6 TESTINGS 7 SILENCE 8 RESET 9 DRILL 4 REDIAL INTERVAL 5 DIALING TYPE 1 TONE DIALING 2 PULSE DIALING 6 LINE ENABLE 1 LINE 1 ENABLE 2 LINE 2 ENABLE 7 LINE 1 RING COUNT 8 REPORT RANGE 1 PANEL WIDE 2 Reserved 3 NETWORK WIDE 9 Reserved 8 NETWORKING 1 NETWORK CARD 1 INSTALLED 2 PORT SUPERVISION 2 NET...

Страница 98: ...e in the software downloads for the FPA 1000 panel on the Bosch web site www boschsecurity com allows off line processing of configuration and settings and uploading of the new configuration file through an Ethernet link or a local personal computer connection Browser based operating and programming allows Downloading of the entire program history file walk test data current status system voltages...

Страница 99: ... When a second user tries to switch to Level 3 access from a web page the user receives a message A level 3 user is already logged in and the user remains at the current level Only a user at the local FPA 1000 keypad has higher access status The user at the keypad can overrule a user who is in Level 3 from a web page by logging in When the local user logs in at the FPA 1000 and requests Level 3 ac...

Страница 100: ...tch to Level 1 without having to re enter your PIN In order to switch from Level 2 to Level 3 you need to go to Level 1 first Then press Logout and the Login and enter the Level 3 PIN After 25 minutes without any action Access Level 2 or 3 become invalid In Level 3 the user is notified one minute before the session expires In Level 2 the user is notified the next time the user triesto perform a Le...

Страница 101: ...zones configure floors for sandwich alarm Networking Indicate network card installation and port supervision specify network wide wiring topology Class A or Class B synchronize network wide settings list networked panels Maintenance Control Individually control all outputs Mainboard relays NACs and City Tie Option Bus LED annunciator test SLC 1 and SLC 2 outputs Testing System information Walk tes...

Страница 102: ...nvalid entries Whenever you enter an invalid value the system provides information about the correct range You cannot leave the input field without entering a correct value Label text The user can set up labels for different applications for example to document the location of a device Generally the label text is limited to a maximum of 20 characters ...

Страница 103: ...e wired so that the control panel s line seizure relay disconnects them when necessary Measure the line voltage while these devices are in use Ensure that it remains above 5 V 3 Check for intermittent faults in the phone line Make a test call and confirm that the line is free of distortion and noise Temporarily exchange Lines 1 and 2 on the control panel and check if the problem indication moves t...

Страница 104: ... 6 45 Off site diagnostic via browser based user interface Task Menu Shortcut View history data 1 HISTORY 1 VIEW HISTORY Print history data 1 HISTORY 2 PRINT HISTORY Perform communicator test 3 TEST MENU 1 COMM TEST View print SLC diagnostics 3 TEST MENU 2 SLCS View voltage level and perform battery load test 3 TEST MENU 3 POWER AND BATT Test relays NACs and SLC outputs 3 TEST MENU 4 OUTPUTS Perfo...

Страница 105: ...eset the loss counter open the browser or off line tool and use SLC 1 Test or SLC 2 Test on the Testing screen 6 4 Power and Battery Test To see displays of voltage levels for AC AUX power and battery use the keypad shortcut 3 3 1 for TEST MENU POWER AND BATT VOLTAGE LEVELS To automatically perform battery tests use the keypad shortcut 3 3 2 for TEST MENU POWER AND BATT TEST BATTERY NACS The syste...

Страница 106: ...rm a battery load test see Power and Battery Test page 105 at least twice per year Replace batteries that fail the test Battery voltage should be 26 V Recommended Battery Manufacturers POWER SONIC PS 1270 PS 12170 PS 12180 YUASA NP7 12 NPG18 12 7 2 Fuse Replacement The fuse is located at the lower left of the mainboard see the following figure Replace with a 15 A blade type fuse only BATT RELAY1 R...

Страница 107: ...eds to be reset Each network card has a small blue button on the top surface of the card Press this button to reset the networking card 7 4 System Reset There is a small blue button to the right of the potentiometer along the bottom edge of the mainboard that acts as a system reset button To momentarily remove power from the panel press this button When the button is released the panel re initiali...

Страница 108: ...cal Mains power supply primary Supervision Supervised for the presence of AC power Voltage 120 VAC 60 Hz 1 1 A maximum or 240 VAC 50 Hz 0 6 A maximum Power supply secondary with battery backup Voltage 24 VDC Supervision Supervised for the presence of AC power Current consumption standby 1 25 A maximum Current consumption alarm 5 A maximum 1 0 A maximum shared between panel and SLC s Panel 250 mA S...

Страница 109: ...o 31 VRMS non switched power limited unfiltered non supervised AUX RST Resettable 500 mA at 24 V FWR 17 to 31 VDC switched power limited filtered non supervised Line impedance for ground fault detection Option Bus SLC NAC secondary power circuit City Tie Local Energy AUX 15 kΩ Option Bus OB Voltage Nominal 12 VDC power limited supervised Current 500 mA maximum Configuration 1 Class B Circuit wirin...

Страница 110: ...75 mm2 City Tie Local Energy Mode Type of connection In series Alarm trip coil 24 VDC Alarm current 250 mA DC momentary Supervisory standby current 50 mA DC Trip coil resistance 14 5 Ω Nominal coil voltage 3 65 VDC power limited supervised City Tie Reverse Polarity Module Nominal voltage Nominal 24 VDC 26 4 VDC maximum power limited supervised Output current 33 mA maximum Supervisory standby curre...

Страница 111: ...kouts 1 2 3 4 and 1 in Connections Pluggable terminal blocks for AUX Option Bus SLC NAC Mainboard Relays and City Tie Wire gauge 12 AWG to 18 AWG ISO 4 mm2 to 0 75 mm2 Material Cold rolled steel 19 gauge 1 2 mm Color Red Dimensions W x H x D 14 5 in X 4 3 in x 22 7 in 36 8 cm x 10 9 cm x 57 7 cm Dimensions with trim ring W x H x D Semi flush mounted H recessed H flush 17 5 in x 25 6 in x 44 5 cm x...

Страница 112: ...lays each Communication circuits Communication circuits Phone line IP connections primary and secondary path via central station receiver 2 x RJ45 Ethernet connections 1 x RJ45 Reporting formats ContactID SIA3000 and Modem IIIa2 Conettix IP reporting Baud rate 2400 bits second PSTN dialing types Pulse only tone and pulse or tone only PSTN test call frequency 4 6 24 hour 7 or 28 days interval indiv...

Страница 113: ...ation Guide 2017 11 2 0 F 01U 173 607 Networking cards FPE 1000 NW connector Twisted pair wire or CAT 5 cable shielded or unshielded 8 4 Panel Address Data Default panel IP address 192 168 1 30 192 168 99 1 Default client IP address 192 168 99 2 Gateway 192 168 1 1 Subnet mask 255 255 255 0 ...

Страница 114: ...vation Act Fail Activation Failure ADDR ADDRS Address Addresses ALM Alarm Annuns Annunciators AUTO Automatic AUX Aux Auxiliary AV Alarm Verification BATT Batt Battery Calib Calibration COMM Communicator or Communication CONFIG Configuration Curr Current D Day Mode DACT Digital Alarm Communicator Transmitter DAY SENSI Day Sensitivities Deact Deactivation Dev Device DIAG Diagnostics Dirt Dirty DRL D...

Страница 115: ...board MIN Minimum Mins Minutes MOD Module MON Monday NAC Notification Appliance Circuit NC Normally Closed nEOL no EOL NO Normally Open OB Option Bus OC Open Collector output Overcurr Overcurrent Overvolt Overvoltage PAS Positive Alarm Sequence PIN Personal Identification Number Pls Please PNT LABEL Point Label Pri Acct Primary Account Proc Fail Process Failure PROG Prog Programming or Programmed ...

Страница 116: ... Secondary SIL Silenceable SLC Signaling Line Circuit SPVR SUPERVSR Supervisory SUN Sunday SW Software SYS System Temp 3 Temporal Code 3 THU Thursday TUE Tuesday TRB Trouble Ver Version VERIFY Verification Volt Voltage w Walk Test Log WED Wednesday WT Walk Test 9 2 Default Programming Site Data Banner Language IP and Printer Banner 1 line BOSCH Banner 2 line Fire System Panel ID empty Panel IP add...

Страница 117: ...sabled Start 1st Sunday in March End 3rd Sunday in October Detector day sensitivity enabled Disabled Mo Tu We Th Fr Sa Su From 7 00 am To 5 30 pm Timer Settings Global delay mode AV PAS Pre signal Day mode No delay Silence inhibit 0 min Investigation time 180 s Alarm verification delay 60 s Sequential reset delay 5 s AC failure delay 3 h Waterflow delay 90 s Waterflow silenceable disabled Auto sil...

Страница 118: ...ress empty Printer IP port 21 Printer FTP user empty Printer FTP password empty Event printing enable Disabled Event print delay 5 s SLC Configuration Device Type Programming Option Default Setting SLC 1 Installed Installed enabled Address 0 fixed Topology 2 x class B Label empty Bypassed Disabled SLC 2 Installed Installed disabled Address 0 fixed Topology 2 x class B Label empty Bypassed Disabled...

Страница 119: ...135 F 57 C RoR Enabled Label empty Day alarm mode Multi combined Day sensitivity Smoke 2 50 ft 8 20 m Day sensitivity Heat 135 F 57 C RoR Enabled Smoke sensor Multi separated Smoke label empty Smoke point type Generic FAP 325 V2F FAP 440 FAP 440 D SMOKE P Zones No zone assigned Delay mode No delay Device LED flashing Enabled flashing when polling Point type Fire automatic Set point 2 50 ft 8 20 m ...

Страница 120: ...ssigned Delay mode No delay Device LED flashing Enabled flashing when polling Point type Fire automatic Set point 135 F 57 C RoR Enabled Label empty Day sensitivity 135 F 57 C RoR Enabled Bypassed Disabled RTI rating Standard FAI 325 SMOKE I Zones No zone assigned Delay mode No delay Point type Fire automatic Set point 0 85 ft 2 80 m Label empty Day sensitivity 0 85 ft 2 80 m Bypassed Disabled FAA...

Страница 121: ... ft 6 55 m Detector bypassed Disabled FAD RLY Duct relay FAD RLY Installed Disabled Zones Global alarm zone 226 assigned FAD RLY label empty FAD RLY bypassed Disabled FLM 325 I4 CONT MOD Delay mode No delay Device label empty Point type Fire alarm manual Input type NO with EOL Zones No zone assigned Bypassed Disabled FLM 325 I4 A FLM 325 I4 AI CONT MOD Wiring type Class B Class A Enabled Disabled ...

Страница 122: ...ode No delay Point type Fire automatic Label empty Bypassed Disabled FLM 325 2R4 FLM 325 2R4 2A FLM 325 2R4 2AI FLM 325 2R4 8A FLM 325 2R4 8AI RELAY MOD Device label empty Relay 1 Relay 2 each Relay label empty Zones Global alarm zone 226 assigned Bypassed Disabled Sequential reset Disabled Drillable Disabled D328A RELAY MOD Label empty Zones Global alarm zone 226 assigned Bypassed Disabled Sequen...

Страница 123: ...signed Drillable Disabled Ext signaling Disabled Bypassed Disabled Energized in normal Enabled Sequential reset Disabled Label Mainboard relay 2 Relay 3 Relay type Supervisory Zones Global supervisory zone 228 assigned Drillable Disabled Ext signaling Disabled Bypassed Disabled Energized in normal Disabled Sequential reset Disabled Label Mainboard relay 3 NACs NAC 1 NAC 2 NAC pattern Steady Zones ...

Страница 124: ...Bus LED Annunciators Zone 1 128 Enabled LCD Annunciators Command Centers No presettings D7035 Octal Relay Modules D7048 Octal Driver Modules Installed Disabled Device label empty Zones Global Alarm Zone 226 assigned Drillable Disabled Ext signaling Disabled Bypassed Disabled Energized in normal Disabled Sequential reset Disabled Label empty FPP RNAC 8A 4C Remote NAC Power Supplies RNAC 1 RNAC 2 RN...

Страница 125: ...ting Conettix Receiver IP address empty Port number 7700 Polling interval 240 s Acknowledge wait time 10 s Anti replay Enabled Encryption Disabled Key string 0 9 A F 32 characters 11 11 11 11 11 11 11 11 11 11 11 11 11 11 11 11 PSTN Communicator Settings Dialing type DTMF Line 1 Enable Disabled Line 2 Enable Disabled Redial interval 10 s Steering For all report steering groups Secondary as backup ...

Страница 126: ... Zone No Local 1 128 Group 129 225 Label empty NAC Pattern Default Bypassed Disabled Counting 1 Floor 0 Set Default Reset Dual zones Group 1 Group 2 Group 3 Dual zone pair 1 No zones assigned Dual zone pair 2 No zones assigned Dual zone pair 3 No zones assigned Dual zone pair 4 No zones assigned Floors Floor 1 to 32 Label empty Sandwich alarm Disabled Networking No presettings 9 3 Compatible SLC D...

Страница 127: ...c Installation and Operation Guide 2017 11 2 0 F 01U 173 607 Type Number Device Group Type Description D324A SMOKE I Analog Ionization Detector Head D326A CONT MOD Analog Point Contact Module D327A NAC MOD Analog NAC Module D331A SMOKE D Analog Duct Smoke Detector ...

Страница 128: ...r Designation 1 TT 2 CAAA FA 1063 SIA DCS Layout Example in the Bottom Row 1 TT Data type code 2 CAAA Address number circuit and address for point event or 000u for user level Tab 9 48 SIA DCS reporting codes layout and abbreviations Modem IIIa2 Receiver Output Explanation When the Modem IIIa2 reporting format is used with a Bosch Security Systems Inc receiver the receiver output is in accordance ...

Страница 129: ...al 17 3 110 CC AAA FH CAAA FIRE ALARM REST Fire Alarm Restore Smoke 18 3 111 CC AAA FH CAAA FIRE ALM RESTOR SMOKE DETCTOR Fire Alarm Restore Duct 19 3 116 CC AAA FH CAAA FIRE ALM RESTOR SMOKE DETCTOR Fire Alarm Restore Heat 20 3 114 CC AAA FH CAAA FIRE ALARM RESTOR HIGH TEMP SENSOR Fire Alarm Restore Manual 21 3 115 CC AAA FH CAAA FIRE ALM RESTOR Fire Alarm Restore Waterflow 22 3 113 CC AAA SH CAA...

Страница 130: ...ne 1 75 1 351 00 000 LT 0000 PHONE LINE FAIL PHONE LINE 1 Phone Line Trouble Line 2 75 1 352 00 000 LT 0000 PHONE LINE FAIL PHONE LINE 2 IP Reporting Path Failure 76 1 356 CC AAA ET CAAA NETWORK FAIL Communication to Primary Account Failure 77 1 350 CC AAA YC CAAA COMM FAI Communication to Secondary Account Failure 78 1 350 CC AAA YC CAAA COMM FAI Short on OUT Connections for Class B 79 1 372 CC 0...

Страница 131: ... Disconnect 105 1 330 CC AAA ET CAAA EQUIPMENT FAIL Wiring Loop Open 106 1 371 CC AAA ET CAAA EQUIPMENT FAIL Network Panel Missing 107 1 300 CC AAA ET CAAA EQUIPMENT FAIL Double Panel Address 108 1 300 CC AAA ET CAAA EQUIPMENT FAIL Network Configuration Conflict 109 1 300 CC AAA ET CAAA EQUIPMENT FAIL Network Panel New 110 1 300 CC AAA ET CAAA EQUIPMENT FAIL Wrong Address Trouble for 440 111 1 380...

Страница 132: ... RESTR Short on OUT Connections for Class B Restore 143 3 372 CC 000 ER CAAA PT BUS RESTORAL Short on IN Connections for Class B Restore 144 3 372 CC 000 ER CAAA PT BUS RESTORAL Short Restore 145 3 372 CC AAA ER CAAA FIRE TBL RESTOR Open Restore 146 3 371 CC AAA ER CAAA FIRE TBL RESTOR Circuit Open Restore 147 3 371 CC 000 ER CAAA PT BUS RESTORAL Low Voltage Restore 148 3 370 CC 000 ER CAAA PT BUS...

Страница 133: ...estore for 440 172 3 380 CC AAA ER CAAA EQUIPMENT RESTORAL CO Lifetime Restore for 440 173 3 380 CC AAA ER CAAA EQUIPMENT RESTORAL CO Fail Restore for 440 174 3 380 CC AAA ER CAAA EQUIPMENT RESTORAL Switch Board New Restore 176 3 330 CC AAA ER CAAA EQUIPMENT RESTORAL Wiring Loop Type Restore 177 3 300 CC AAA ER CAAA EQUIPMENT RESTORAL Control Conflict Restore 178 3 300 CC AAA ER CAAA EQUIPMENT RES...

Страница 134: ...134 en Appendices Analog fire panels 2017 11 2 0 F 01U 173 607 Installation and Operation Guide Bosch Security Systems Inc Mainboard Address Assignment page 39 ...

Страница 135: ...K Turns off the piezo and starts the investigation timer after a PAS activation or the trouble reminder for trouble events if configured A built in piezo provides an audible indication of the system status The panel offers three different programmable authority levels The PIN needed for authority levels 2 and 3 and restricted Level 1 if programmed is a four digit code After pressing the enter key ...

Страница 136: ...when inputs or outputs or other elements are bypassed Flashing Silent When the panel is not operating or when a walk test is in progress Off Silent When no trouble condition exists or when the panel is resetting 1 Short beep upon every key press 2 When the panel is in the normal state no alarm supervisory or trouble condition the display message is System Normal along with the current date and tim...

Страница 137: ...ns off the piezo and starts the investigation timer after a PAS activation or the trouble reminder for trouble events if configured A built in piezo provides an audible indication of the system status The panel offers different programmable authority levels The PIN needed for authority Levels 2 and 3 and restricted Level 1 if programmed is a four digit code After pressing the enter key the user is...

Страница 138: ...when inputs or outputs or other elements are bypassed Flashing Silent When the panel is not operating or when a walk test is in progress Off Silent When no trouble condition exists or when the panel is resetting 1 Short beep upon every key press 2 When the panel is in the normal state no alarm supervisory or trouble condition the display message is System Normal along with the current date and tim...

Страница 139: ......

Страница 140: ...Bosch Security Systems Inc 130 Perinton Parkway Fairport NY 14450 USA www boschsecurity com Bosch Security Systems Inc 2017 Bosch Sicherheitssysteme GmbH Robert Bosch Ring 5 85630 Grasbrunn Germany ...