D9068
|
Operation and Installation Guide | Appendix F: D8024/D10024/D10024A Analog
FACP Operation
.
Bosch Security Systems, Inc. | 3/13 | F01U071094-0
7
69
F.4.5 Sample Reports
lists the sample reports and the data sent to the central
Appendix C: Fire Communicator Report Summary
on page 56 for
information on the Equipment Fail Codes.
does not show the event text that can be sent in Modem IIIa
2
format.
Table 21: Sample Reports
SIA
Contact ID
Report Description
Code
Description Code
Description
Modem IIa
2
Printer Text
Point Fire
Alarm Point 21,
Loop 3, Panel 5
FA421
Fire alarm
1 110 05
421
Fire alarm
Fire Alarm Area=5
Point=421
Fire Point
Trouble Point 10,
Loop 1, Panel 2
FT10
Fire
trouble
1 373 02
010
Fire
trouble
Fire Trouble Area=2
Point=010
Low Battery on
Panel 1
YT
System
battery
trouble
1 302 00
000
Low system
battery
Battery Low
All Events Cleared
RR
1 305 00
000
Re-boot
Peripheral 10
failed on Panel 3
ET110
Equipment
failure
condition
1 333 03
110
System
trouble
Equip Fail SDI=110
Cond=003
FACP Ground Fault,
Panel 2 (Equipment
Fail #17)
ET17
Equipment
failure
condition
1 333 17
002
System
trouble
Equip Fail SDI=002
Cond=017
General Disable
(any device on
Panel 4 disabled -
Equipment Fail
#32)
ET32
Equipment
failure
condition
1 333 32
004
System
trouble
Equip Fail SDI=004
Cond=032
General Disable
Restoral (Panel 4
no longer shows
disables -
Equipment Restoral
#32)
ER32
Restoral
3 333 32
004
System
trouble
Equip Restoral
SDI=004 Cond=032
Fire Drill Start
Panel 2
FI
Fire Test
begins
1 607 00
002
Walk Test
Mode
Fire Walk Start
ID=002
Fire Drill End
Panel 2*
FK
Fire Test
ends
3 607 00
002
Walk Test
Mode
restore
Fire Walk End ID=002
Silence from
Panel 1
KB1
Heat or
bypass
1 400 00
000
Open or
close
Alarm Silence ID=001
Relay=001
*
Report is not supported at this time.